OmniMetrix Hero 40 Amp Tap Commander Installation Manual

Advertisement

Quick Links

The 40 Amp Tap Commander ™ connects to the Rectifier and Hero 1 or Hero 2 Rectifier Monitor and
allows the user to adjust the output voltage of the rectifier locally, remotely via OmniView or
automatically to keep the rectifier output current relatively constant.
1. Verify the following components are included in the package and are free from damage:
Tap Commander Module
Tap Commander Interface Cable (6')
Tap Power Cable
14 Yellow Tap Wires
Snap-Track (for mounting the Tap Commander)
Installation Instructions
2. Before installing the Tap Commander:
Using a multimeter, measure and record the Shunt Voltage
Using a multimeter, measure and record the Output Voltage
Using a multimeter, find and mark two Taps that measure 11-15 VAC between them. These
will be Power Taps for the 40 Amp Tap Commander.
Install the Hero RMU (see installation guide included with the Hero)
During the installation of the Hero, route the Tap Commander Accessory cable through the
conduit. See the note on the next page if you must cut the 4 pin connector off.
Make sure the current protection wires are firmly screwed down on the external Interrupter
Relay connections.
Turn on the AC power to the rectifier and confirm the
is blinking once per second (this can take up to ten minutes)
The external Interrupter Relay must be wired correctly and operational before installation
of the Tap Commander.
o
Hero 1 – Test the Interrupter Relay by issuing a Rectifier Off command from
Omniview. Confirm the relay is open by using a multimeter to measure mV across
the shunt, the mV reading should be zero. After confirmation, issue a Rectifier On
command from Omniview.
o
Hero 2 - Test the relay by pressing and holding the red "Interrupter Relay" button
for three seconds, on the Hero 2 Interface Board. The
below the red "Interrupter Relay" button signifying the relay is open. Confirm the
relay is open by using a multimeter to measure mV across the shunt, the mV reading
should be zero. After confirmation, press and hold the red "Interrupter Relay"
button until the
Interface Board are only active when the blue Heartbeat light is flashing.
The external Interrupter Relay is an integral part of the Tap Commander design. If the
external Interrupter Relay is not working correctly, do not proceed with installation of the
Tap Commander until that problem is resolved
3. Installation:
Power down the AC to the Rectifier
Remove the shorting bars from the rectifier
Document No.: IM-1508
Author: T. Robinson/C Fisher
Hero
40 Amp Tap Commander
Red LED
goes out on the Interface Board. NOTE: The button on the
Revision Level: 03
Approved By: C. Fisher
1
Installation Guide
Blue Heartbeat LED
on the Hero board
Red LED
should illuminate
Approval Date: 10-JUNE-2020

Advertisement

loading

Summary of Contents for OmniMetrix Hero 40 Amp Tap Commander

  • Page 1 Hero 40 Amp Tap Commander ™ Installation Guide The 40 Amp Tap Commander ™ connects to the Rectifier and Hero 1 or Hero 2 Rectifier Monitor and allows the user to adjust the output voltage of the rectifier locally, remotely via OmniView or automatically to keep the rectifier output current relatively constant.
  • Page 2: Power Connection

    Hero 40 Amp Tap Commander ™ Installation Guide • Mount the Tap Commander inside the Rectifier (It can rest free on the bottom screen, be mounted on the door or back of the rectifier, mounting materials not included) • If necessary, route the interface cable through the conduit from the Hero to the rectifier. If the 4 pin connector must be removed in order to route through the conduit, insert stripped wires according to the diagram below, otherwise plug in the 4 pin connector as shown.
  • Page 3 Hero 40 Amp Tap Commander ™ Installation Guide If the 4 pin connector has to be removed in Connect wires from Power order to insert the Taps here. cable in the conduit, strip and insert the wires here according to the diagram below.
  • Page 4 Hero 40 Amp Tap Commander ™ Installation Guide • Route the yellow Tap Wires except for the Common wires to the appropriate taps on the rectifier. Each Tap Wire is labelled on both ends as follows: COARSE COMMON, COARSE 1, COARSE 2, … COARSE 6 FINE COMMON, FINE 1, FINE 2, …...
  • Page 5 Hero 40 Amp Tap Commander ™ Installation Guide For Hero 1 or Hero 2 units: Jumper will be installed in either the H1 or H2. 40A Tap Commander Kit for Hero reference_designator QTY UOM item_name vendor_1 vendor_item_number_1 1 40A Tap Commander 1 each 40A Tap Commander Power Cable OMX 402105...