G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50Hz G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz OPERATION & MAINTENANCE MANUAL Original Instruction This manual contains important safety information and must be made available to personnel who operate and maintain this machine. 46689183_en_B_05/19...
GENERAL DATA CONTENTS GENERAL DATA ..............................ELECTRICAL DATA ..............................G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
Diesel fuel Crush Warning manual before operation or No open flame. maintenance of this machine is undertaken. No Water Coolant Fill Earthing Point G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
Do not operate Genset if fuel has been spilled inside or near the unit. G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
, shall be used for the external earth conductor, when earthing is required. qualified, licensed electrical contractor, knowledgeable in local codes, should be consulted. G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
Ensure that maintenance personnel are adequately trained, competent and have read the Maintenance Manuals. G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
Page 15
Transport When loading or transporting machines ensure that the specified lifting and tie down points are used. G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
Do not remove the cap from a HOT engine radiator. regulations. The sudden release of pressure from a heated cooling system can cause severe injury or death. G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
8. With main breaker “ON” power is present and available for use. 9. Close side doors for optimum cooling of the unit while running. G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
MENU NAVIGATION Used for navigating the instrumentation, event log and configuration screens. For further details, please see section entitled ‘Operation’ elsewhere in this manual. G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
The LCD backlight is on if the unit has sufficient voltage while the unit is turned on, unless the unit is cranking for which the backlight is turned off. G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
Page 23
Coolant temperature instrumentation screen. Mains failure. Flexible sensor instrumentation Appears when a scheduled run is screen. active. Appears when the event log is being displayed. G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
Page 24
Appears when a USB connection is made to the controller Appears if either the configuration file or engine file becomes corrupted. G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
Page 25
Generator Under The generator output frequency has fallen below the pre-set Frequency prealarm setting after the Safety On timer has expired. G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
Page 26
Maintenance due for oil filter. Alarm Air Filter Maintenance Maintenance due for air filter. Alarm Fuel Filter Maintenance Maintenance due for fuel filter. Alarm G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
Page 27
Delayed Over Current level for a configured duration. The measured kW has risen above the configured trip level kW Overload for a configured duration. G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
Page 28
The level detected by the fuel level sensor is above the High Fuel Level high fuel level pre-set alarm setting. G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
Page 29
Maintenance due for oil filter. Air Filter Maintenance Alarm Maintenance due for air filter. Fuel Filter Maintenance Alarm Maintenance due for fuel filter. G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
If the Auto Mode button is not pressed, the display automatically returns to the Home Page after the configured setting of the LCD Scroll Timer. G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
Page 31
These pages contain electrical values of the mains, measured or derived from the module's voltage inputs. • Mains Voltage (ph-N) • Mains Voltage (ph-ph) • Mains Frequency G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
'wake' the module, press any fascia control buttons. Power Save Mode in the DSE Configuration Suite Software. Select Stop/Reset mode. The generator is stopped. G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
'on load' runs. Once the generator has been placed on load, it is not automatically removed. To manually remove the load either: G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
09:00 on Monday and run for 5 hours, then start at 13:30 on Tuesday and run for 30 minutes. G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
Page 38
If the engine is running OFF LOAD in Auto Mode and a scheduled run configured to 'On Load' begins, the set is placed ON LOAD for the duration of the Schedule. G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
Check battery supply is present on the Starter output of module. Ensure oil pressure switch or sensor is indicating the 'low oil pressure' state to the controller. G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
(refer to appendix). at rest Check that sensor is compatible with the module and that the module configuration is suited to the sensor. G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
When editing a configuration using the fascia editor, be sure to press the Auto Mode button to save the change before moving to another item or exiting the fascia editor. G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
In the event that a part must be replaced, only genuine parts as defined by the parts list (PARTS BOOK) should be used. Doosan shall not be held liable for any critical damage or faults which may be caused by the use of unauthorized or remanufactured parts.
The turbocharger will be hot and can cause severe burns. Always allow the turbocharger to cool before carrying out any maintenance. G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
CAUTIONS FOR INSPECTION AND REPAIR 1. Inspection and repair of engine should be performed only when the engine is stopped. G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
9. Discard oil according to the regulations set forth by the relevant authorities. G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
Always use coolant mixed with antifreeze. If coolant faults to engine for which Doosan shall not be held liable. without antifreeze is used, the coolant may freeze causing the coolant passage in the cylinder block to Consider the following while managing engines: freeze and damage the engine.
INSPECTION AND REPAIR OF THE ENGINE.......................54 CHECKING ENGINE PARTS AFTER PROLONGED OPERATION ..............54 INSPECTION AND REPAIR OF TURBOCHARGER ..................54 INTAKE SYSTEM .............................54 EXHAUST SYSTEM ............................54 LUBRICATION SYSTEM ..........................54 G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
Page 52
6) Do not operate the alternator without battery connection. G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
Page 53
BREAK-IN PERIOD OF THE ENGINE GENERAL INFORMATION CAUTION Doosan engines are subjected to a final approval test to ensure the provision of high quality engines before being shipped. However, engines are not operated for a long The oil pressure may increase with high rpm and period of time in this test.
Page 54
As parts related to exhaust and weather or areas with cold climate. When replacing turbocharger are used at high temperature, be careful not engine oil, use of Doosan genuine engine oil is to mix the bolts and nuts with other parts when recommended.
60Hz 310PS 344PS (1,800 rpm) (228kW) (253kW) NOTE: All data is based on operation without cooling fan at ISO 3046. (Production tolerance: ±5%) G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
Serial Number (5 digits) After engine model SUFFIX (2 digits) • Type 4 New representative specification (9 digits) Production Year (1 digit) Serial Number (5 digits) G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
Such accessories may become stuck in rotating parts while the engine is running and may cause serious bodily injury. G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
Using unauthorized or remanufactured parts may cause critical P086TI damage and faults to engine for which Doosan shall not be held liable. CHECKING THE COOLANT COOLING SYSTEM GENERAL INFORMATION DANGER The coolant should be replaced according to the cycle specified in the inspection interval table.
Page 74
3) Compare the color of the test sheet (C) to the color coolant once a year. of NITRITE of the standard color table. G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
Recooled charge air to intake pipe (max. 50 °C) CAUTION To keep the optimum performance of the air cooler, clean it regularly. G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
SAE 15W40 API CD OR CE ABOVE P086TI SAE 15W40 API CD OR CE ABOVE NOTE: Use of Doosan genuine engine oil is recommended. G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
Exceeding the upper limit may damage the engine. Be careful not to let foreign substances flow into the engine when replenishing engine oil. DV2213163A G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
Replenish fuel while the engine is stopped. Apply a skin protective cream after cleaning from oil. Do not put oil-stained gloves or cloth in pockets. G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
The quality of fuel is very important to satisfy the engine performance, extension of engine life and the allowable exhaust gas level. Doosan engines are designed to use diesel fuel available in the local market. If the optimum engine performance is required, select the proper fuel by referring to the fuel selection table below.
Water in the fuel system may stop the engine. Use approved fuel only. Use of non approved fuel may result in increased water in the fuel filter. G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
Do not inhale the atomized fuel oil. If 4. Coil spring possible, work under an extraction system. 5. Guide bush normal abnormal abnormal DV2213024A G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
• Scrape needle seat with cleaning cutter. Dip cutter in test oil before use. The cutter can also be clamped in G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
Page 86
6. After adjusting the injection timing, disassemble the “U” shape pipe and readjust the delivery valve and the 9. Install the oil delivery pipe and return pipe. valve spring. G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
Be careful not to let dust inside when assembling the DV2213029A air filter. Air cleaner assembly. G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
EDL022156A NOTE: Do not reuse damaged elements under and circumstances. When in doubt, replace the element with a new one. G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
Be sure to soak only impeller. The turbocharger should be supported by a bearing housing and not by an impeller. G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
(“-” minus wire) of the battery. Short circuit may occur while working on the electrical system. Reconnect the ground wire last after completing all of work. G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
Apply tester to belt at a point midway between two pulleys so that edge of contact surface (2) is flush with the V-belt. G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
Page 94
Tighten fixing bolts and nuts. d) To change the V-belts loosen fixing bolts and nuts. Then push the alternator toward water pump pulley by hand. G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
Digital inputs and PID auto setup functions for PID control parameters • Application of digital clock for fault timing and engine operating hours G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
Page 96
DC 24V (12V to 30V) Current Consumption 120mA Operating Temperature -20 to +70°C Storing Temperature -30 to +80°C Operating Humidity 0 to 95% G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
A and B of the actuator regardless of their polarities. Wiring should be 18AWG (105?) or better and the outside should be wrapped by plastic tubes for insulation or insulated mesh lines. G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
Input information should immediately apply to the controller system once updated. G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
Page 99
LED turns on in red where there are fault conditions. At this moment, the LCD display is not activated, and Doosan logo will appear for 1 second followed by the operation display after pressing the LCD button.
Page 100
It offers menu to monitor the controller operation. It shows values for Engine RPM, Valve Duty, Valve Current, Aux RPM Input, Pickup Voltage and Bat Voltage. G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
Page 101
Users can designate the maximum current values when the generator is in full load. 13) N-LOAD CURR Users can designate the operating current values of the actuator when the generator has no load. G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
Page 102
Default setup will change the configuration values of the engine to the default values. To initiate default setup, you need to select YES and then press Enter button. Press No button if you don't want to. G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL...
Step 4) The controller will activate the actuator with power supply and pick-up sensor input. When the power is supplied, and the pick-up terminal delivers normal sensor inputs as the engine starts, the controller activates the actuator. G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
2) When problems described in alarm codes E03, E04, E07 or E08 occur, the engine will not be able to restart as long as the alarm is not released. 3) When alarms occur, you can release them by turning off the power of the controller. G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
Page 105
If the LED does not turn on, cut the power off and contact our A/S center for service request. Step 4) Check whether the power LED turns on and Doosan logo appears on the LCD display after supplying power to DC +24V input terminals (-E, +F) of the battery.
Do not allow children younger than 14 to go near the air outlet guards. G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
CONTRAINDICATIONS TO USE Use of the machine is restricted to operating conditions (environment, speed, voltage, power, etc.) compatible with the characteristics indicated on the nameplate. G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
Page 110
R1-R2 - External voltage trimmer (remove ST1) 50 Hz 60 Hz R791T R150 Black Black Black Consult R150 manual Blue ref. 5384 Green/yellow G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
The room where the alternator is placed must be ventilated to ensure that the ambient temperature cannot exceed the data on the nameplate. G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
Ensure that the alternator has the degree of protection matching the defined environmental conditions. When the alternator’s power output is ensured directly through cables, these must be connected before start-up. G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
R 180 (220V < U < 240V) : L1 => T2, L2 => T3 In case of reconnection, ensure that the AVR voltage detection is correct ! G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
The earth terminal (ref 28) is connected to the frame. The connections inside the terminal box must never be subjected to stress due to cables connected by the user. G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
(**) - Revolving field coil open circuit or short-circuited (**) Warning: The AVR internal protection may cut in (overload lost connection, short circuit). G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
Page 118
Assembly A: Connect a 12 V battery in series with a rheostat of approximately 50 ohms - 300 W and a diode on both exciter field wires (5+) and (6-). G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
CAUTION The screws for fixing the feet on the housing and immobilising the stator must not be removed (bolt of the stator lower). G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
Page 120
• After extraction, be careful with the fan. It is necessary to replace the fan in case of disassembling. G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
Page 124
* M12 (only with TAL 044 L and M) ** 69 N.m (only with TAL 044 L and M) ***130 N.m (only with TAL 044 L and M) G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
BREAKER ADJUSTING INSTRUCTIONS ELECTRONIC TYPE: S150 TO S250 SERIES TIME / CURRENT CHARACTERISTIC CURVES Under bar is default setting. Electronic Type G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...
BREAKER ADJUSTING INSTRUCTIONS ELECTRONIC TYPE: S400 AND S600 SERIES TIME / CURRENT CHARACTERISTIC CURVES Under bar is default setting. Electronic Type G80XW/XF, G115XW/XF, G150XW/XF, G200XW/XF - 50HZ OPERATION & MAINTENANCE MANUAL G100XW/XF, G135 XW/XF, G170XW/XF, G225XW/XF - 60Hz...