DECLARATION OF CONFORMITY Description MONO/ MULTI DC INVERTER ARIA-ARIA Modello - Model ELSKOV-12 ELSKOV-18 ELMOV2-14H5 ELSKOV2-18 ELSKOV3-24 Is in compliance with the follow ECC direcrives, latest modification included, and the relevant nationale granting regulations in force: 2004/108/CE 2006/95/CE 2003/108/CE 2011/65/CE 2012/2016/CE...
Page 3
INDEX chapter page 1. GENERAL INFORMATION 2. DESCRIPRION 3. PRELIMINARY CHECKS 4. INSTALLATION 5. MAINTENANCE OF UNITY 6. COMPATIBILITY...
1. GENERAL INFORMATION 1.1 SYMBOLOGY Within this publication and / or inside the equipment we used the following symbols: USER: Information, paragraph, chapter WARNING: Calls attention to actions that, Manual affecting the user or the user. if not correctly performed, may cause serious injury.
GENERAL INFORMATION 1.3 OBSERVATIONS Keep the manual in a dry location to avoid deterioration. The device must be installed in such a way as to make carefully read and understood all the information contained possible the maintenance and / or repair. in this manual.
Page 6
GENERAL INFORMATION 1.6 OPERATING LIMITS Temp. Indoor [°C] Temp. Outdoor [°C] Thermal power Max. 27/- 24/18 Cooling capacity Max. 32/23 43/26 The operating temperature (outside temperature) for cooling is of 18/43 ° C. For the heat pump is -7/43 ° C. 1.7 BEFORE INSTALLING Before installing the equipment read carefully and keep the 7.
Page 7
DESCRIPTION ension of the unit dimensions: mm 2.2 COMPONENTS AND MEASURES ELSKOV-12 Outline dimension of t Outline dimension of the unit SAVH12A-A1NB(O) Outline dimension of th SAVH12A-A1NB(O) SAVH12A-A1NB(O) nsion of the unit Outline dimension of the unit Φ198 SAVH12A-A1NB(O) Φ198 Φ198 Φ198 FA-NA、SUV3-H24/1TFA-NA...
INSTALLATION 4. INSTALLATION 4.1 PLACE OF INSTALLATION The installation location should be agreed with the customer, - The front panel must be inspected, so the front space paying attention to the following points: should be adequate to permit the operator with all the steps required during installation, maintenance and assistance - The equipment should be placed in a technical room of (controls, adjustments, refrigerant charge).
Page 10
INSTALLATION 4.3 INSTALLATION MODE ELSKOV-18 Air output Air output Inlet air invisible unit perimeter wall invisible unit perimeter wall Maximum distance to the wall: 2 linear meters, 8 m long Maximum distance to the wall: 2 linear meters, 8 m long version.4 holes Ø...
Page 11
outdoor unit. ● Make sure the support can withstand at least four times INSTALLATION of the unit weight. ● The outdoor unit should be installed at least 3cm above the the floor in order to install drainjoint. ● For the unit with cooling capacity of 2300W~5000W, 6 4.7 DRAINAGE PIPE expansion screws are needed;...
Page 12
INSTALLATION 4.13 ASSEMBLY PROCEDURE The condensing ELFO SHALL BE INSTALLED IN - Connect the unit and connecting pipes condensing unit Inner. POSITION ACCESSIBLE technician in safely, otherwise the CAT (service centers) may refuse the intervention. - Connect the vacuum pump to the fitting (suction), set in THE CONDENSING MUST NOT BE INSTALLED AS motion and make sure that the needle drops to - 0.1 MPa OUTSIDE IN WINTER MAY CAUSE DAMAGE.
INSTALLATION The presence of air and moisture in the refrigerant system • For each of the refrigerant circuits, acting pressurize the may have the following side effects: tubes from the gas exhaust valve: PROVA DI TENUTA TUBAZIONI E VUOTO • Increased pressure in the system 1.
Installation of outdoor unit INSTALLATION 3. Pretightening the union nut with hand. 4. Tighten the union nut with torque wrench by referring to the sheet below. Hex nut diameter Tightening torque (N . m) pipe joint diameter pipe [mm] tightening torque [Nm] Φ...
INSTALLATION 4.20 PERFORMANCE OF EMPTY • Use a pump to run the vacuum, it is strictly forbidden to hour. If after 3 total hours the pressure is not yet dropped drain the coolant. below -755 mmHg, you have to find the leak and repair it. •...
INSTALLATION 4.22 LEAK DETECTION 1. Check for leaks with leak detector. Apply soap and water in the suspected position and maintain the soap and water for more than 3 minutes. If there are 2. If the leakage probe is not available, please use soap and bubbles coming out from this position, identify and restore water for leak detection.
MAINTENANCE UNIT 5. MAINTENANCE UNIT 5.1 ORDINARY MAINTENANCE Regular maintenance is essential to maintain the efficiency of - Efficiency safeties. the unit both in terms of operation and energy. - Power supply voltage. The maintenance plan that the Technical Assistance - Power consumption.
Page 18
MAINTENANCE UNIT 5.4 FAULTS AND POSSIBLE REMEDIES Anomalia Causa Rimedio U/INS/CAT Power failure Verify the presence of voltage main switch in pos. OFF Check the upstream safety systems low supply voltage Check power line The compressor does not start Fault compressor condenser Replace the part compressor failure Replace the part...