Power Inspired Willo User Manual

Outdoor integrated ups solution

Advertisement

Quick Links

Outdoor Integrated UPS Solution
User Manual

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Willo and is the answer not in the manual?

Questions and answers

Summary of Contents for Power Inspired Willo

  • Page 1 Outdoor Integrated UPS Solution User Manual...
  • Page 2: Table Of Contents

    Table of Contents INTRODUCTION.......................... 2 ⚠WARNINGS ..........................2 INSTALLATION ......................... 3 Location..........................3 Mounting & Securing ......................3 Grounding ..........................4 Battery Assembly ........................4 AC Power Connections ......................6 Equipment Installation ......................6 UPS Installation ........................6 Operation ........................... 7 Starting Up ..........................
  • Page 3: Introduction

    1. Installation of the cabinet should only be undertaken by trained and competent personnel. 2. Hazardous AC Voltages appear within the Willo Cabinet. Although the risk of accidental contact is minimised with the use of covers, access to the cabinet should only be performed by personnel trained in the risks involved.
  • Page 4: Installation

    Willo Instruction Manual INSTALLATION Location. 1. Ensure good ventilation, avoiding dust as much as possible and avoid areas which may be subject to excessive standing water. 2. The cabinet should be placed on a firm flat surface with minimal inclination.
  • Page 5: Grounding

    Read the warning section in this manual. 2. The Willo cabinet can house up to 6 x 100Ah batteries in the lower 2 tiers. 3. For ease of assembly and for safety, batteries should be installed one at a time and in the same orientation as follows: 4.
  • Page 6 Willo Instruction Manual 9. Insert battery 3 into the cabinet as shown. 10. Remove the cover from battery 2 positive terminal and connect the link wire from battery 3 -ve terminal to battery 2 +ve terminal. 11. Remove the cover from battery 3 positive terminal and connect the +ve cable from the Anderson lead (coloured red or brown) to battery 3 positive terminal.
  • Page 7: Ac Power Connections

    Willo Instruction Manual AC Power Connections 1. The AC input and output power cables are fed into the Willo cabinet through the oval cut outs in the floor of the unit at the front. 2. The AC input and output terminals are located on the door of the shelf of Tier 3. Remove the cover to access the terminals.
  • Page 8: Operation

    6. The UPS should now be completely switched off, and the loads will be off. 7. Before carrying out any maintenance on the power distribution panel, ensure that the AC supply feeding the Willo cabinet is disconnected. Maintenance 1. Maintenance should only be carried out by competent persons and involves checking live AC sources.
  • Page 9: Appendices

    Appendices Surge Protection Device The distribution panel of Willo contains a Surge Protection Device (SPD) based upon Metal Oxide Varistor (MOV) technology connected between live, neutral and the earth conductors to protect the internal electronics from over voltage surges caused in particular by nearby lightning strikes.
  • Page 10: Snmp

    Willo Instruction Manual SNMP The UPS inside Willo may be fitted with an internal SNMP card. This allows communication with the UPS over a network. The SNMP device allows some control of the UPS via the network: Remote Battery Test The UPS can be instructed remotely to perform a battery test, either for 10 seconds, a set number of minutes, or until the battery reaches a certain threshold.
  • Page 11: Key Specifications

    Willo Instruction Manual Key Specifications Cabinet Dimensions Total 635 x 410 x 1120 Usable 600 x 410 x 1000 Weight (Cab Only) 70kg IP Rating Rating 1KVA / 900W Voltage Rating 230V Nominal (160V – 295V input window) Battery String Battery Charger 2x 4.5A...
  • Page 12 DOC:WILLO-MANUAL REV 1.4...

Table of Contents