Battery And Breaker Diagrams (240 Vdc) - Tripp Lite 3-Phase Battery Cabinet Extended-Run Owner's Manual

Extended-run 3-phase battery cabinet
Table of Contents

Advertisement

6 – Diagrams
(continued)

6-3 Battery and Breaker Diagrams (240 VDC)

Shelf 1 (Bottom)
To Fuse or Breaker
Notes:
• All internal wiring is UL-listed, MTW, 125C Hi-Flex cable.
• Terminal block is UL-recognized and rated for 600 VDC.
• Breaker is UL-listed and rated for 150 A, 600 VDC, 25 KAIC.
• Cabinets with breakers are shipped with the breaker in the off/open position.
• Battery arrangements shown are typical but may vary depending on cabinet and battery type.
Shelf 2
Shelf 3
Termination
To UPS
Positive
To UPS
Negative
[12]
Battery
Positive
Battery
Negative
UL-Listed
Breaker

Advertisement

Table of Contents
loading

Table of Contents