Maintenance; Specifications - UTC Fire and Security Edwards Genesis WG4 Series Installation Sheet

Outdoor horn
Table of Contents

Advertisement

Available languages

Available languages

Figure 3: Wire slot and jumper locations
(1)
(3)
JP1
(1) Wire slot
(2) JP3 horn volume jumper
Wiring
See Figure 4. Connect all wiring in accordance with national
electrical codes and applicable local requirements.
Equipment hazard. To avoid equipment damage,
Caution:
ensure that the signal voltage does not exceed the voltage
rating of the device.
Figure 4: Wiring diagram
(1)
(2)
(3)
JP1
(1) Horn-Strobe in −
(2) Horn-Strobe in +
(3) Marking indicates the signal
polarity required to activate
the device
P/N 3101999-ML • REV 1.0 • ISS 11APR12
(2)
JP3
(3) JP1 horn pattern jumper
(4)
(5)
JP3
(6)
(4) Horn-Strobe out –
(5) Horn-Strobe out +
(6) Not used

Maintenance

Do not change the factory finish.
Perform a visual inspection and an operational test twice a
year, or as directed by the local authority having jurisdiction.
This unit is not serviceable or repairable. Should the unit fail to
operate, contact the supplier for replacement.

Specifications

Operating voltage
24 VDC, 24 VFWR nominal
Dimensions (W × H × D)
5.6 × 8.5 × 1.4 in. (142 × 216 × 36 mm)
Sound level output
See Table 4, Table 5, Table 6, and
Table 7
Horn tone
3.2 kHz
Wire size
12 to 18 AWG (0.75 to 2.50 mm²)
Compatible electrical box
Outdoor
Model 449
Indoor
4 in. square by 1.5 in. deep box
Operating environment
Temperature
−40 to 151°F (−40 to 66°C)
Relative humidity
0 to 95% noncondensing
Table 4: Sound pressure level (dBA), per UL 464
Volume Setting
16V
Continuous High
89.7
Continuous Low
85.4
Temporal High
84.2
Temporal Low
81.7
dBA = Decibels, A-weighted.
UL 464: Sound level output measured in a reverberant room at 10 ft.
(3.05m).
Table 5: Sound pressure level (dBA), per CAN/ULC-S525
Volume Setting
16V
Continuous High
94.0
Continuous Low
92.8
Temporal High
96.5
Temporal Low
90.3
dBA = Decibels, A-weighted.
CAN/ULC-S525: Sound level output measured in an anechoic room at
10 ft. (3.05m).
Table 6: Directional sound characteristics (horizontal pattern), per
CAN/ULC-S525
Angle (°) [1]
Sound output (dBA)
90 (Ref)
0 (Ref)
60 and 115
−3
45 and 132
−6
[1] Angles are measured from a perpendicular axis; positive angles to
the right.
24V
33V
94.7
97.4
89.5
92.5
90.5
93.5
85.4
88.1
24V
33V
99.6
102.9
97.2
98.6
100.5
104.2