Download Print this page

Edwards Signaling AdaptaBeacon 90 Series Installation Instructions

Signals

Advertisement

Quick Links

Cheshire, CT 06410 203-699-3300 (Ph)
203-699-3365 (Cust. Serv. Fax)
203-699-3078 (Tech. Serv. Fax)
90 Series
Description
The catalog series 90, 92 (120 and 240V AC Models only) and 95
AdaptaBeacon signals are UL and cUL listed, general purpose
visual and visual/audible signaling appliances. The 90 and 92
series signals are strobe lights; the 95 signals are strobe lights with
a single pulsing horn.
The 92 series single flash beacons are available in 120VAC, 240V
AC and 250V DC models. The 240V AC and 250V DC versions
have a larger lens assembly than the 120V version. The 92(*)-S1
beacons are supplied with 3 ft (.9 m) flying leads.
The 90, 92 and 95 series are suitable for indoor or outdoor (weath-
erproof) installation and utilize a standard base that allows direct
surface mounting, mounting on a 4" (102 mm) octagon box, or
mounting on 1/2" (13 mm) NPT conduit. When installing in-
doors, the signals may be mounted in any position. For outdoor
installation, the signals must be mounted on conduit with their
lens or dome facing directly up.
Electrical Specifications
Catalog
Rated
Number
Voltage
90(*)-N5
120V 50/60 Hz
92(*)-N5
120V 50/60 Hz
92(*)-R5
240V 50/60 Hz
92(*)-S1
250V DC
95(*)-N5
120V 50/60 Hz
*The letter (A - amber, B - blue, C - clear, G - green, M -
magenta or R - red) in this position signifies the color the
supplied lens.
Installation Instructions for Catalog Series 90, 92 and 95
AdaptaBeacon
92-N5 Series
Current
0.10 Amp
0.10 Amp
0.05 Amp
0.10 Amp
0.10 Amp
®
Signals
92-R5 and 92-S1
Series
Installation
WARNINGS
To prevent electrical shock, ensure that power is
disconnected before installing the signal.
To prevent leakage and a potential electrical hazard,
use care when disassembling the signal to prevent
tearing of the weatherproof gaskets. If a
component resists removal due to adhesion to a
gasket, do not force apart by hand; carefully
separate the components by prying them apart with
a thin blade screwdriver.
90, 92, and 95 Series
1.
Remove the base from the signal using one of the following
applicable procedures.
a.
90 Series: See Figure 1. Remove the screw in the clamp
ring, remove the ring and lift the dome off the signal.
Loosen the three screws in the base of the lens, turn the
lens clockwise and lift it straight up and off of the strobe
tube support plate, being careful not to damage the strobe
tube. Remove the two screws that are partially set into
the raised area of the strobe tube support plate. Then,
grasp the socket (on the strobe tube support plate) and
carefully lift the support plate off of the signal base.
Pull the wires leads out of the conduit entrance hole in
the base. Proceed to step 2.
b.
92 and 95 Series: See Figures 2 and 3. Remove the screw
in the clamp ring and remove the ring.
For the 92-N5 and 95 series, lift the lens/lamp assembly
off of the base and pull the wire leads out of the conduit
entrance hole in the base.
For the 92-R5 and 92-S1 series, lift the lens off of the
signal base, remove the strobe tube support plate and
pull the wire leads out of the conduit entrance hole in the
95 Series
P-047550-0898 ISSUE 9 © 2003

Advertisement

loading
Need help?

Need help?

Do you have a question about the AdaptaBeacon 90 Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Edwards Signaling AdaptaBeacon 90 Series

  • Page 1 Installation Instructions for Catalog Series 90, 92 and 95 ® AdaptaBeacon Signals Cheshire, CT 06410 203-699-3300 (Ph) 203-699-3365 (Cust. Serv. Fax) 203-699-3078 (Tech. Serv. Fax) 90 Series 92-N5 Series 92-R5 and 92-S1 95 Series Series Description Installation The catalog series 90, 92 (120 and 240V AC Models only) and 95 WARNINGS AdaptaBeacon signals are UL and cUL listed, general purpose visual and visual/audible signaling appliances.
  • Page 2 base. Exercise care so as to not tear the gaskets that are permanently attached to the lens and signal base. Proceed to step 2. For indoor installation, the signal may be direct surface mounted, mounted on a 4" (102 mm) octagon box, or mounted on 1/2"...
  • Page 3 knock-out holes in the base. Proceed to step 3 for wiring Strobe Tube Replacement connections. CAUTIONS Mounting on 1/2" (13 mm) NPT Conduit To prevent damage to the strobe tube, lift the lens WARNING straight up and off of the signal. To prevent leakage and a potential electrical hazard, when mounting outdoors the signals must be To prevent damage to the strobe tube, handle the...
  • Page 4 Clamp ring Lens (Catalog No. V93-L*) Gasket (permanently affixed to lens) Strobe tube Strobe tube base Strobe tube socket (attached to support plate) Signal base Figure 5. Replacing the Strobe Tube Figure 4. Replacing the Strobe Tube on the 92-N5 Series Signals Figure 6.

This manual is also suitable for:

Adaptabeacon 92 seriesAdaptabeacon 95 seriesAdaptabeacon 90 n5 seriesAdaptabeacon 92 n5 seriesAdaptabeacon 92 r5 seriesAdaptabeacon 92 s1 series ... Show all