Pfannenberg ICPlus902 User Manual page 6

Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
English
7. Cooling
7.1.
The regulator gets the temperature measure from the thermoregulation probe; the setpoint is 16,5°C + 3°C for
Water+Glycol units and 24,5°C + 3°C for OIL units.
Control action is proportional to the error and it reaches saturation (100%) when the temperature is greater than the setpoint
plus the "Hysteresys" = 3°C.
Type
EB/RACK Water+Glycol
EB/RACK Oil
All EB/RACK
6
Cooling with Fixed Setpoint
Compressor Setpoint Settings
Parameter
SEt
SEt
WS
Df1
70040-089_01-A.docx
Factory Setting [°C]
16,5
24,5
SEt + "Df1"/2
3
Range of Setting [°C]
10 - 35
20 - 35
11,5 - 35
3