Download Print this page

Honeywell ML7295 Series Product Data page 4

Spring return direct coupled actuators

Advertisement

ML7295 SPRING RETURN DIRECT COUPLED ACTUATORS
CAUTION
Deteriorating vapors and acid fumes
can damage the actuator.
Install actuator in areas free of acid fumes and other
deteriorating vapors that can attack the metal parts of
the actuator.
Location
Install the actuator in a location that allows enough clearance
for mounting accessories and for servicing.
Refer to Warnings and Cautions (above) for locations to avoid.
Mounting
The ML7295 DCA has a self-centering shaft coupling to
accommodate specific shaft lengths, sizes, and shapes. Proper
actuator location and means of actuator rotation prevention are
necessary to avoid excessive strain on the output gear.
The ML7295 DCA operates a damper or hydronic valve by
driving the shaft either cw or ccw, depending on the design.
All actuators are shipped with a 5° preload on the spring.
When power is applied to the actuator, the preload is released
and the actuator spring-returns 5° for tight closeoff.
The ML7295 DCA is designed for single-point mounting.
Single-point mounting is typically used when the actuator is
mounted on a damper frame. A mounting bracket (see Fig. 1)
is provided for installing the actuator.
CAUTION
Avoid damage to the damper or actuator.
Do not allow the mounting bracket to bind or clamp
the actuator to the duct.
Use the mounting bracket only to prevent the actuator
housing from rotating.
Preparation
Before installing the ML7295 on the shaft, determine the
opening direction of the damper or valve for correct spring
return rotation and wiring connections. The ML7295 can be
mounted to provide clockwise or counterclockwise spring
return.
Determine appropriate mounting orientation
See Fig. 2 for mounting orientation.
CW TO OPEN
CCW TO CLOSE
(FAIL-SAFE
POSITION)
Fig. 2. ML7295 Spring Return Direct Coupled
Actuator mounting orientation.
63-2539—1
CW TO CLOSE
(FAIL-SAFE
POSITION)
CCW TO OPEN
M12443
Measure shaft length
If the shaft is less than three inches in length, the shaft coupling
must be located between the damper/valve and actuator
housing. If the shaft length is more than three inches, the shaft
coupling may be located on either side of the actuator housing.
If the coupling must be moved from one side of the actuator
to the reverse, follow these instructions (see Fig. 3):
1. Remove the position indicator from the shaft coupling
and set it aside for later use.
2. Remove the retainer clip from the shaft coupling and
set it aside for later use.
3. Remove the shaft coupling from one side of the actuator.
4. Replace the shaft coupling on the opposite side of the
actuator aligning it with the mark on the housing.
5. Replace the retainer clip on the shaft coupling using the
inner groove of the coupling.
6. Replace the position indicator on the shaft coupling.
If the shaft coupling is located between the actuator housing
and damper/valve, the position indicator holder must be
attached to the other side of the actuator. If this is necessary,
perform the following (see Fig 4):
1. Slide the position indicator holder onto the shaft
coupling near the retainer clip and rotate it until it snaps
into place.
2. Place the position indicator on the holder.
Fig. 3. Mounting shaft coupling to opposite side of actuator.
Fig. 4. Adding position indicator holder.
4
M12441
M12440

Hide quick links:

Advertisement

loading

This manual is also suitable for:

Ml7295aMl7295cMl7295h