AS Martem Data Concentrator TELEM-GW5 1. Main Tasks The tasks of the Data Concentrator TELEM-GW5 (GW5) include the following: • To control and monitor the system from the control center using data communication protocols IEC 60870-5-101 and IEC 60870-5-104 • To concentrate data collection from lower level peripheral devices and control them by using different data exchange protocols 2.
AS Martem Data Concentrator TELEM-GW5 4. View Figure 4 a) GW5 with Ethernet port, b) with optical port 5. Technical Data Data communication protocols • To higher or lower level systems IEC 60870-5-101 or IEC 60870-5-104 • To lower level devices in addition to IEC 60870-5-103, ModBus, Telem,...
Page 5
AS Martem Data Concentrator TELEM-GW5 Communication ports 1 - For connecting the GPS system for time synchronization if Switch 2 • is in OFF position and for loading a program if Switch 2 is in ON position 2 - For connecting dial up modems (RS-232 interface signals DSR, •...
AS Martem Data Concentrator TELEM-GW5 Emission Conducted to communication lines EN55022-5-2 • Conducted to power supply lines EN55022-5-1 • Emitted EN55022-10-3-5 • 6. Typical Application for Electric Power Station Time synchronisation Data contcentrator Digital outputs TELEM GW5 Digital inputs moduls...
AS Martem Data Concentrator TELEM-GW5 8. Indication For operation Green LED – Blinking green indicates that the program is running Red LED – Failure For communication Yellow LED – RX Green LED – TX Green LED at SSP port – blinking indicates the existence of GPS time synchronization 9.
Page 8
AS Martem Data Concentrator TELEM-GW5 3. Open loader F2812SeriaFlash.sdp 4. Open the Project tab => Settings Akadeemia tee 21G Tel: +372 639 79 79 E-mail: martem@martem.ee 12618 Tallinn Fax: +379 639 79 80 www.martem.ee Estonia - 8 -...
Page 9
AS Martem Data Concentrator TELEM-GW5 5. Choose Com Do not use bigger than C3 (Com 3). 6. Show the way to the target. If the gw5.out file is in the same catalogue as SDFlash.exe (the program that you use for firmware update) then gw5.out is sufficient. However, if you want to download firmware from some other place then you have to show the exact way, for example, C:\GW5\ Firmware\…\gw5.out...
Page 10
AS Martem Data Concentrator TELEM-GW5 7. Coff load Open the Buffer tab => Coff Load 8. Reset Open the Device tab => Reset Akadeemia tee 21G Tel: +372 639 79 79 E-mail: martem@martem.ee 12618 Tallinn Fax: +379 639 79 80 www.martem.ee...
Page 11
AS Martem Data Concentrator TELEM-GW5 9. Start programming Open the Device tab => Flash Start the Program If the connection with the target has failed then reset GW5 (switch 1) and repeat the last step (position 9). If Erase-, Program- and Verify have succeeded, close the window and move the GW5 set switch „Firmware update mode“...
AS Martem Data Concentrator TELEM-GW5 10. GW5 Configuration Tool 10.1 Getting Started When starting the GW5 configuration program, user interface window with the main menu is opened: Figure 10. 1.1 User interface window Warning Check communication – If there is no connection with the GW5 device then a warning message is displayed together with an alarm beep (Figure 1).
AS Martem Data Concentrator TELEM-GW5 Fields in the communication parameters window • Port – PC communication port which is used to communicate with GW5 • Baud rate – Data communication rate • Parity – Use of parity control bit Flow control – Determines whether the RTS/CTS handshaking is used •...
AS Martem Data Concentrator TELEM-GW5 Table of configuration window menu items Main Submenu (shortcut key) menu File Open Save Save Exit (Ctr+N) (Ctr+O) (Ctr+S) Common Read Write Send TCP/IP General Modem Config Config Reset Settings Settings Settings (Ctr+R) Ctr+W) Tools...
Page 15
AS Martem Data Concentrator TELEM-GW5 Figure 10.3 .1 Configuration window with an advanced Port configuration tab card Configuration parameters of a port: • Protocol – Communication protocol used by all the devices of this port. Each protocol name is accompanied with a symbol l”^” or ”ν ” which indicates whether the port is used for an uplink or a downlink channel.
AS Martem Data Concentrator TELEM-GW5 • Query Timeout in milliseconds - Query timeout for devices on downlink channels • Query Timeout count – Count of timeouts after which the error flag is raised and the query of this device temporarily suspended •...
Page 17
AS Martem Data Concentrator TELEM-GW5 Adding devices By clicking on the shortcut icon, a new device with default settings is added. It is also possible to add new devices with a right mouse click which makes the extended control menu to appear.
AS Martem Data Concentrator TELEM-GW5 Clearing Devices To clear the Device Tab Card, select Clear from the extended control menu. A warning window always appears before removing operations are concluded: Select Yes to accept or No to cancel the removal operation of the devices.
Page 19
AS Martem Data Concentrator TELEM-GW5 Columns: Type – Object’s type: digital input (DI), digital output (DO), analog input (AI), counter (CN) Sub Type^ – Object’s subtype for uplink. The following dialog box opens on clicking: Subtypes of object and time marking mode can be selected.
Page 20
AS Martem Data Concentrator TELEM-GW5 • Invert – Object’s value will be inverted • Fn.code – Function code on the IEC 60870-5-103 protocol • Info no. – Information number on the IEC 60870-5-103 protocol • Index – Object index on the IEC 60870-5-103 protocol. It indicates the order number of the object in message types 3 and 9 of analog measurements.
Page 21
AS Martem Data Concentrator TELEM-GW5 Adding Objects By clicking on the button, a new device with default settings is added. Objects can also be added with a right click on the device tab card. After that the following extended control menu appears:...
AS Martem Data Concentrator TELEM-GW5 10.3.4 Formulas Tab Card Figure 10.3.4 Formulas tab card Columns: • Type, Sub Type, Sub Type , Invert, Object Adr ^, DeadB, Crit.Value, Raw Min, Raw Max, Scale Min, Scale Max, Forb.Ports, obj. - as in Objects Tab Card •...
Page 23
AS Martem Data Concentrator TELEM-GW5 Operators Oper. Obj. type Description Sample *Priority DI/AI Addition @101+3,2 DI/AI Subtraction @101-0,49 DI/AI Multiplication @101*2 DI/AI Division @101/2 DI/AI Exponentiation @101^2 < Greater than @101<0,499 > Less than @101>0,5 DI/AI Square sqr(@101*10) sqrt DI/AI...
AS Martem Data Concentrator TELEM-GW5 • Formula rows can also be added, removed or cleared by using the extended control menu like in the Object Tab Card. It appears with a right mouse click on the Formula Tab Card. To add a Formula, select Add Formulas, to remove a Formula, select Remove Formula and to clear all formulas, select Clear.
AS Martem Data Concentrator TELEM-GW5 11. Common Main Menu 11.1 TCP/IP Settings Only used for GW5 with Ethernet port to determine IP parameters. 11.2 General Settings To determine device initialization timeouts and time zone correction. Akadeemia tee 21G Tel: +372 639 79 79 E-mail: martem@martem.ee...
AS Martem Data Concentrator TELEM-GW5 11.3 Telephone Modem Settings Modem Settings are used to determine calling parameters in the dial-up mode operation. The modem can be used only through communication port 2. Only this port has all the necessary handshaking signals for the modem.
AS Martem Data Concentrator TELEM-GW5 Number Checking may be enabled for incoming calls. In this case, the connection may be established only from these 5 phone numbers maximum. (The phone numbers must be typed up exactly as the modem receives them).
Page 28
AS Martem Data Concentrator TELEM-GW5 Signal RJ45 RJ45 Cable GW5 - Telem RTU Port 1 Port 2...7 Pin Pin Signal Tx- (422) Connected: RJ45 - RJ45 Tx+ (422) 8 - 1 7 - 2 6 - 3 5 - 4...
13. Notes • If not stated otherwise on the individual pages of this document, AS Martem reserves the right to make modifications. • Although the contents of this publication have been checked for conformity with the hardware and software described, we cannot guarantee complete conformity since errors cannot be excluded.
Need help?
Do you have a question about the TELEM-GW5 and is the answer not in the manual?
Questions and answers