MOUNTING DIRECTLY TO A SHELF

The shelf should be flat and level within ± 0.5
mm (± 0.02 in.). If there are any noticeable gaps
between the breaker and the shelf, fill them in
using flat washers as spacers.
Check to make sure the breaker On-Off indicator
shows OFF (green), then mount it by following
the steps below:
1. Fasten the breaker onto steel angles or to a
flat plate (Fig. 13). Use M8 hex head bolts
(either 50 mm or 35 mm). The tightening
torque should be 120-150 kgf-cm (9-11 ft-lb).
2. Either mounting method shown in (Fig. 14)
may be used.
INSTALLATION
Fig. 13 Mounting Breaker to Flat Plate or
Angles
PANEL
ANGLE
M8 x 35MM OR M8 x 50MM BOLT
Fig. 14 Optional Hardware Orientation