Specifications

These specifications assume the MediaChecker was
calibrated using 100 ft (30 m) (or more) of cable of the
same type and batch as the cable being measured.
Accuracy is specified for two years after calibration.
Coax Termination Measurements
Any loop resistance value between 5 Ω and 350 Ω is
interpreted as a terminator resistance. Resistance values
below 5 Ω are considered shorts; resistance values
greater than 350 Ω are displayed as >350 Ω.
Input Connectors
RJ45, DB-9, and BNC
Input Protection
Will withstand connection to any of the supported
networks in a live condition with a supply voltage not
exceeding 25 V.
"ACTIVE CABLE" is displayed and an audible signal
sounds when the MediaChecker is connected to a cable
with voltage present.
ATTENTION: Never connect the
MediaChecker to any telephony inputs,
systems, or equipment, including ISDN.
Table 17. Cable Test Characteristics
Network
Cable
DeviceNet
Thick and
Thin
DeviceNet
KwikLink
DH+/RIO
Blue Hose
or similar
ControlNet
RG6,
RG6F,
DS3/4
Ethernet
UTP/FTP
Specifications
Wiring
Pass/Fail Pins
DeviceNet
Data pair, power
pair, shield
DeviceNet
Data pair,
power pair
DH+
Data pair, shield
Coaxial
Center pin and
shield
EIA/TIA
Wire pairs 1, 2;
4-pair
3, 6; 4, 5; 7, 8
Also the foil
(shield) for FTP
1788-UM002A-US-P – April 2000