Troubleshooting
If your POLAR appliance develops a fault, please check the following table before making a call to the Helpline.
Fault
The appliance is not working
The appliance turns on, but the
temperature is too high/low
The appliance is leaking water
The appliance is unusually loud

Error Messages

The following table details the cause and subsequent response of the appliance to errors.
Error Message
(flashing)
The inner temperature exceeds
HtA
the set maximum temperature
The inner temperature exceeds
LtA
the set minimum temperature
Short circuit or interruption of
PF1
the thermostat probe input line
Short circuit or interruption of
PF2
the evaporator probe input line
Inner temperature greater than
HLA
90°C
Inner temperature lower than
LLA
-45°C
The alarm message will end when the alarm trigger is no longer present, except PF1 and PF2 that require the appliance to be turned Off, then On again.
Technical Specifications
Model
Voltage
Power
230V 50Hz
250W
VRX1200/330
230V 50Hz
250W
VRX1500/330
230V 50Hz
250W
VRX1800/330
230V 50Hz
250W
VRX2000/330
Probable Cause
The unit is not switched on
Plug and lead are damaged
Fuse in the plug has blown
Power supply
Internal wiring fault
Too much ice on the condenser
Condenser blocked with dust
Doors are not shut properly
Appliance is located near a heat source or air flow
to the condenser is being interrupted
Ambient temperature is too high
Unsuitable foodstuffs stored in the appliance
Appliance is overloaded
The appliance is not properly levelled
The discharge outlet is blocked
Movement of water to the drain is obstructed
The water container is damaged
The drip tray is overflowing
The frame has become loose
The appliance has not been installed in a level or
stable position
Cause
Display flashes
Alternating error message and current temperature
Display flashes
Alternating error message and current temperature
Display flashes
Display flashes
Display flashes
Alternating error message and current temperature
Display flashes
Alternating error message and current temperature
Temperature
Current
Range
1.1A
2°C to 10°C
1.1A
2°C to 10°C
1.1A
2°C to 10°C
1.1A
2°C to 10°C
Check the unit is plugged in correctly and switched on
Check doors are shut and seals are not damaged
Move the refrigerator to a more suitable location
Increase ventilation or move appliance to a cooler position
Remove any excessive hot foodstuffs or blockages to the fan
Reduce the amount of food stored in the appliance
Check installation position and change if necessary
Appliance Response
Capacity
5 x Gastranorm ¼ Container
7 x Gastranorm ¼ Container
9 x Gastranorm ¼ Container
10 x Gastranorm ¼ Container
4
Action
Call RWA agent or qualified Technician
Replace the fuse
Check power supply
Call RWA agent or qualified Technician
Defrost the appliance
Call agent or qualified Technician
Adjust the screw feet to level the appliance
Clear the discharge outlet
Clear the floor of the appliance
Call RWA agent or qualified Technician
Empty the drip tray
Check and tighten all nuts and screws
Action
Check Troubleshooting Guide
If problem persists call RWA agent or
qualified Technician
Check Troubleshooting Guide
If problem persists call RWA agent or
qualified Technician
Compressor operates as specified by
parameter '=23 '
Defrost as specified by parameters d8 and d9
Call RWA agent or qualified Technician
Call RWA agent or qualified Technician
Dimensions
Refrigerant
H x W x D (mm)
430 x 1200 x 335
430 x 1500 x 335
R134a
430 x 1800 x 335
R134a
430 x 2000 x 335
Weight