Download Print this page

Olimpia electronics SLD-28/SP Manual

Self testing maintained illumination signs with white led’s

Advertisement

Quick Links

SELF TESTING MAINTAINED ILLUMINATION SIGNS WITH WHITE LED's
TECHNICAL CHARACTERISTICS
Mains voltage
Maximum power consumption
Battery (Ni-MH)
Battery protection
Indications
Recharging time
Minimum emergency duration
Light source intensity (230V) / (emerg.)
Degrees of cover protection
Produced in accordance with
Operation temperature range
Relative humidity
Construction materials
External panel's dimensions
External unit's dimensions
Typical weight
Guarantee
Thank you for purchasing this product of
Olympia Electronics. A European manufacturer.
GENERAL
The luminaire consists mainly from two parts,
the body, where all the electronics are located
and the lamp-head where the indication sign
and the high efficiency LEDs are located.
Maintained to non-maintained selection
capability
Power on the device and press continuously
the TEST button for 10 seconds, until the led
strip turns off. Release the button and after a
short emergency test, the device operates as
non-maintained. If you want to restore the
previous condition (maintained operation),
press continuously the TEST button for 10
seconds, until the led strip lights. Release the
button and after a short emergency test, the
device operates as maintained illumination
sign.
Installation
To install the illumination sign follow the
installation instructions on page 2.
Battery Cut-off
The luminaire enters in this operation when the
mains power supply fails and battery has lost
its energy. During this operation the luminaire
enters the idle state and battery consumption
is negligible, in order to be protected from deep
discharge.
Page 1 from 3
High Quality European based Manufacturers
SLD-28/SP
220-240V AC/50-60Hz
9 VA
Overcharging and full discharging protection
Charge LED, Lamp LED, Fault LED
85lm /85lm
EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3, EN 1838
Bayblend FR3010, aluminum, plexiglas
280x120x15mm
790gr.
3 years (1 year for the battery)
Battery charging
The battery charging is completely controled. In
this case, is achieved the perfect
maintenance , as well as the elongation of its
duration. When the battery has completely
charged, it charges with a maintenance current.
Manual Test
The manual test can be conducted only if the
main power supply and the battery is
connected. By pressing the test button briefly
an operation test is initiated. During this test
period all indication LEDs are OFF.
Automatic test
This test includes all the operations that
provide the manual test and is conducted
automatically every 15 days. In order to be
performed, the main power supply and the
battery should be connected
Automatic Autonomous Test
The Automatic autonomous Test is conducted
and measures the luminaire`s back up
operation. This test is conducted automatically
every six months. In order to be performed, the
main power supply and the battery should be
connected (the battery should be charged). If
the battery is not charged, the test is
postponed until the battery is completely
charged. If during the Automatic Autonomous
Test the luminaire's duration is lower than the
named, then the battery must be replaced.
SLD-34/SP
9.5 VA
3.6V/1.5Ah
24h
3h
105lm /105lm
IP 30
o
0
to
40 C
up to 95%
340x190x15mm
289x65x34mm
1110gr.
922044006_09_020
SLD-44/SP
440x240x15mm
1580gr.
battery

Advertisement

loading

Summary of Contents for Olimpia electronics SLD-28/SP

  • Page 1 High Quality European based Manufacturers SELF TESTING MAINTAINED ILLUMINATION SIGNS WITH WHITE LED’s SLD-44/SP SLD-28/SP SLD-34/SP TECHNICAL CHARACTERISTICS Mains voltage 220-240V AC/50-60Hz Maximum power consumption 9 VA 9.5 VA Battery (Ni-MH) 3.6V/1.5Ah Battery protection Overcharging and full discharging protection Indications...
  • Page 2 Back Up Operation AC Charge The autonomous duration of battery during Good charge current. emergency mode is at least the one that is Οff: No battery (No charging current or stated in the list of the first page. During disconnected battery). emergency mode, a LED strip test is also performed.
  • Page 3 Mounting methods When the device is mounted externally it can use the A-1028 mounting box. Ceiling mounting Wall mounting Placing the mounting springs Α-3018 A-3018 mounting springs Mounting springs for recess mounting A-3018 Recess mounting in suspended ceiling In recess mounting installation the required opening is 280 x 50 mm.

This manual is also suitable for:

Sld-34/spSld-44/sp