Back Up Operation
The autonomous duration of battery during
emergency mode is at least the one that is
stated in the list of the first page. During
emergency mode, a LED strip test is also
performed.
Resetting Errors
Push the Test button for 5 seconds, to
extinguish all the indicated LED errors.
Then the luminaire enters regular operation
mode.
Indication LED status (with connected mains
power supply).
Installation instructions
1
Remove the front plastic cover by unscrewing the two
retaining screws.
2
Pass the mains cables thru the hole of the plastic base.
3
Connect the live and the neutral wires to the terminal block
as shown in picture.
4
Mount the device by installing the included mounting
accessories in the holes or use the Α-3018 mounting
springs for suspended seiling mounting.
Install LED strip and batery connectors to the appropriate
5
PCB connectors.
6
Refit the front plastic cover by srewing the two
removed screws in step 1, and power on the device.
NOTE!!
After finishing the installation you must power the device
at least for 24 hours for battery charging to perform the
named autonomy.
ATTENTION!!
To disconnect the panel ' s cables, you have to power off the mains power supply and
disconnect the battery.
General:
1. Operations for installation, maintainance or testing must be done by authorized personel only.
2. The device must be connected to the mains power supply thru a fuse dependent by the total
amount of the line's power load.
3.
In case of battery or light source replacement, these must be replaced by parts of the same
type, by the manufacturer or by a competent person.
4
. In case of inactive use for a period greater than 2 months, disconnect the battery by pulling
out the battery's connector.
5. I s not allowed to discard batteries in to common trash bins, they must be discarded
t i
only
in battery recycling points. Do not incinerate.
Page 2 from 3
AC Charge
On:
Good charge current.
Οff:
No battery (No charging current or
disconnected battery).
Lamp fault
Οn:
faulty LED strip.
Off:
Good LED strip.
Fault
Οff:
Blink (With AC Charge LED ON): Autonomy or
low battery problem (the battery must be
replaced).
Blink (With AC Charge LED Off):
No charging current or disconnected battery.
2
Battery OK.
1
3
L
N
4
5
922044006_09_020