Section 3
Commissioning
IEC18000345 V1 EN-US
Figure 4:
Any other protection devices in the same CT secondary circuit must not be influenced in any
way (for example, transformer differential protection or ground fault relays).
14
In the case of systems, that evaluate the neutral current, the differential current
of the neutral measurement must be checked as well. A neutral current has to
be simulated in a symmetrical power system to perform the stability test.
Testing the through-fault stability of the neutral circuit.
© Copyright 2019 ABB. All rights reserved
14000045-IEC18000345-1-en.vsd
Distributed busbar protection REB500
1MRK 505 401-UEN B
Commissioning manual