Service Functions Oem; Info Display; Frost Warning - Baxi QAA73.110 Basic Documentation

Room unit for boiler control with opentherm interface
Table of Contents

Advertisement

Description
Line 150
Effect
Description
Line 151
Note
Effect
58/70
Siemens Building Technologies
HVAC Products

Service functions OEM

5.11 Info display

The Info display can be made to appear continuously or temporarily.
1.
Press the line selection buttons to select line 150.
2.
Press the + / - buttons to select the display mode.
Setting range
Temporary, continuously
This setting selects the display mode of the Info display:
When entering X:
Temporary
The information selected on the Info level is displayed for only 8
minutes. After that period of time, the display will return to the standard
display (actual room temperature, time of day and time pointer)
Continuously The information selected last with the Info button will be continuously
displayed.

5.12 Frost warning

A frost warning can be generated depending on a selectable outside temperature.
1.
Press the line selection buttons to select line 151.
2.
Press the + / – buttons to select the required function.
Setting range
– – . –
/ –10 ... +10
– – . – no frost warning
If the outside temperature falls to the selected temperature level or drops below it, the
Info display shows the actual outside temperature as a flashing value.
Basic Documentation QAA73.110 Room unit
Error! Style not defined.
Unit
Unit
°C
Factory setting
Temporary
Factory setting
3.0