4.2 Domestic Hot Water Setup Wizard
From the Home Screen, press
<SETTINGS> in the lower right
corner to load the "Main Menu"
screen shown to the right.
Touch <Setup Wizard> to launch
the "Setup Wizard" screen shown
at the far right. If prompted for a
Service Level 1 passcode, enter
"4321" and press <ACCEPT
PASSWORD> to proceed.
The first step of the Setup Wizard
asks if the MACH 'n' Roll
operating as "Standalone Boiler" or
"Boiler in Cascade System".
Select <Standalone Boiler> and
press <NEXT> to proceed.
Next, the Setup Wizard asks which
modes the MACH 'n' Roll
using: "Comfort Heat" or "Domestic
Hot Water". Make sure that only
<Domestic Hot Water> is
selected and press <NEXT>.
For Pool Heater models, program the NURO as Domestic Hot Water being the pool water values.
Revised: January 3, 2020
Released: January 3, 2020
unit is
unit is
The next step of the Setup Wizard explains the Relay Instructions.
®
The NURO
labeled RELAY A through RELAY D. The factory-default settings are
recommended for most installations, but customization is possible.
For more information on the configurable relay outputs, please refer
to the NURO Boiler Controller: Advanced User's Guide, Part Number
is 1004905979. Press <NEXT> to proceed.
The relay assignments must agree with the wiring to/from the
boiler. For example, if Relay A is user-configured to enable/disable
the Boiler Pump, the control wires to operate the boiler pump must
be properly wired to the Relay A terminals in the High Voltage
(TB2) terminal block. Press the "Next" button to continue.
Make sure that RELAY C is assigned to "DHW Boiler Side Pump".
If not, press <RELAY C>, then select <DHW Boiler Side Pump>
and press <NEXT> to continue.
NOTE: If using an aquastat installed in the domestic water storage
tank, proceed to
installed in the domestic water storage tank, proceed to
4.2.2.
 Patterson Kelley 2020
All Rights Reserved.
control system features four configurable relay outputs
NOTE
Section
4.2.1. If using a temperature sensor
1004905989 MnR & MnRP 300-399-500-750-
®
P-K MACH
Gas Fired Appliance
Technical Service 1.877.728.5351
Section
1050 NURO Rev C (Jan-2020).docx
Page 28

Advertisement

Table of Contents
loading

Table of Contents