10.2 Problem Symptoms and Measures
Symptom
None of the units
operates
Operation
sometimes stops.
Equipment
operates but
does not cool, or
does not heat
(only for heat
pump)
Large operating
noise and
vibrations
Water leakage
Check Item
Check the remote control
Check the power supply.
Check the indoor PCB
Check the temperature
setting
Check the power supply.
Check for faulty operation
of the electronic
expansion valve
Diagnosis by service port
pressure and operating
current.
Check the installation
condition.
Check the installation
condition
Check the air deflector
Check the drain pipe
Check the system
pressure
Details of Measure
Check to make sure that the remoter is ok,the
remote control display is not weak
Check to make sure that the rated voltage is
supplied.
Check to make sure that the indoor PCB is not
broken
Check to make sure that the temperature
setting is not consistent with the ambient
temperature
A power failure of 2 to 10 cycles can stop air
conditioner operation.
Set the units to cooling operation, and
compare the temperatures of the liquid side
connection pipes of the connection section
among rooms to check the opening and closing
operation of the electronic expansion valves of
the individual units.
Check for insufficient gas or somewhere
leakage
Check to make sure that the required spaces for
installation (specified in the Technical Guide,
etc.) are provided.
Check whether the indoor unit is out-of-level
Check the direction of the air deflector;
Set High fan speed and set the temp higher.
Clean the air filter
Check the drain pipe is not blocked, broken,
bended, or the outside-end higher than inside
end ?
Check whether the system pressure is too low
27
Service diagnosis