Important note for the connection of the external input (see Table 2)
For activation of the functions use potential-free contacts, e. g. coupling relays or tra-
cers.
Use separate potential-free contacts for each indication device.
If the functions of several devices shall be operated in parallel, the triggering disconnec-
ting elements (relay outputs, coupling relays etc.) are to be operated in parallel.
Operational earth or other "GND" potentials are inappropriate as common reference po-
tential.
Use a momentary contact for triggering (momentary time 1-5s), but not a permanent
contact.
MV interface
Terminal No.
Designation
1
2
U1
3
U2
4
U3
RS485/MODBUS interface
Terminal No.
Designation
1
COM
2
RES
3
RES
4
RES
5
B
6
A
5.

Device configuration and commissioning

5.1.
Device configuration
ComPass B is delivered with a standard factory setting (see Appendix A) which, in most cases,
meets all requirements. Some parameters (see Table 5) however need to be set and checked indi-
vidually which can be carried out either via the front panel control or the RS485/MODBUS interface.
Any alteration in the configuration should be carried out while assuring that the ComPass B is
supplied by an external supply, otherwise parameter storage may fail.
ComPass B 4023841-001
Assignment
Earth
Voltage/Phase 1
Voltage/Phase 2
Voltage/Phase 3
Table 3:
Terminal assignment of MV interface
Assignment
Common
Reserved
Reserved
Reserved
D1/RS485 "B"
D0/RS485 "A"
Table 4:
Terminal assignment of RS485/MODBUS interface
Instructions for Use
Direction
Input/Output
Input
Input
Input
Direction
Input/Output
Reserve
Reserve
Reserve
Input
Input
15