Produal HML User Manual page 2

Advertisement

Jumper settings
Range selection
S1
* = factory setting
Output selection
S2
* = factory setting
CALIBRATION
The transmitter calibration interval is one year.
HML can be calibrated by using HMV exchange kit. A new calibration report is delivered with the exchange kit.
Using HMV exchange kit
1.
2.
3.
4.
5.
6.
7.
8.
9.
10. Fit the cable connector or connect the cable leads.
11. Connect the display cable (HML-N).
12. Fit the cover.
13. Connect the power supply.
Produal Oy
Keltakalliontie 18, 48770 Kotka FINLAND
0...100 ppm
0...300 ppm *
0...10 Vdc *
4...20 mA
Disconnect the power supply.
Remove the cover.
Disconnect the display cable (HML-N).
Disconnect the cable connector or disconnect the cable leads.
A. Cable connector
Unscrew the filter.
Unscrew the circuit board fixing screws.
Remove circuit board from the housing.
Set the exchange kit jumpers to match the removed board.
Place the exchange kit inside the housing and fit the fixing screws.
Tel: +358 10 219 9100 / Fax: +358 5 230 9210
Information is subject to change without prior notice.
USER GUIDE
www.produal.com