Siemens WL Series Operating Instructions Manual page 343

Low voltage insulated case circuit breaker
Table of Contents

Advertisement

WL Circuit Breaker Accessory Ratings
Manual Operating Mechanism with Mechanical Closing
Closing/charging stored energy mechanism
Manual Operating Mechanism with Mechanical and Electrical Closing
Charging stored-energy mechanism
Closing solenoid and Shunt Trip
Motor Operating Mechanism with Mechanical and Electrical Closing
Spring charging motor
For motor and closing solenoid short-circuit
protection
Auxiliary Release
Undervoltage release (UVR)
Maximum actuating force required on hand
lever
Number of hand lever strokes required
Coil voltage tolerance
Power consumption (5% duty cycle)
Minimum closing solenoid actuation signal
required
Motor voltage tolerance at 120V AC, 240V
AC
Extended tolerance for battery operation at
24V DC, 48V DC, 125V DC, 250V DC
Power consumption of the motor
Time required for charging the stored-energy
mechanism
Short-circuit protection
Standard slow-blow cartridge
Operating values
AC Coil voltage tolerance at 120V AC, 240V
AC
DC Extended tolerance for battery operation
at 24V DC, 48V DC, 125V DC, 250V DC
Rated contrl supply voltage
Power consumption (inrush / contiuous)
Opening time of the circuit breaker for AC /
DC
UVR (no time delay), 2 settings
Setting 1
Setting 2
UVR (with time delay)
Adjustable delay
Reset by additional NC direct opening
24V DC
48V DC
120V AC /
125V DC
240V AC /
250V DC
24 - 60V
110 - 250V
≥ 85% (circuit breaker can be closed)
35 - 70% (circuit breaker opens
AC 50/60Hz
V
DC
V
AC
VA
DC
W
ms
ms
ms
s
ms
52 lbs
9
14 - 28V DC
28 - 56V DC
70 - 140V DC
104 - 127V AC
140 - 280V DC
208 - 254V AC
180Y / 104V AC
220Y / 127V AC
120W for 50ms
50ms
85 - 110%
70 - 126%
110W
≤ 10s
6A
3A
85 - 110%
85 - 126%
120, 240
24, 48, 125, 250
200 / 5
200 / 5
200
80
200
0.2 to 3.2
≤ 100
25 – 4