LG UU36WR Installation Manual page 16

Table of Contents

Advertisement

INSTALLATION OF OUTDOOR UNIT
16
Piping length and the elevation
• Single Operation
1) Standard Inverter
Pipe Size mm(inch)
Capacity
(kBtu/h)
Gas
9
Ø 9.52 (3/8)
12
Ø 9.52 (3/8)
18
Ø 12.7 (1/2)
24
Ø 15.88 (5/8)
30
Ø 15.88 (5/8)
36
Ø 15.88 (5/8)
42
Ø 15.88 (5/8)
48
Ø 15.88 (5/8)
60
Ø 15.88 (5/8)
2) Compact Inverter
Pipe Size mm(inch)
Capacity
(kBtu/h)
Gas
18
Ø 12.7 (1/2)
24
Ø 15.88 (5/8)
30
Ø 15.88 (5/8)
36
Ø 15.88 (5/8)
If installed tube is shorter than 7.5 m,
additional charging is not necessary.
Additional Refrigerant
= [A-7.5 (m)] x Additional refrigerant (g/m)
The installation of pipe-work shall be kept
to a minimum.
Length A(m)
Liquid
Standard
Ø 6.35 (1/4)
7.5
Ø 6.35 (1/4)
7.5
Ø 6.35 (1/4)
7.5
Ø 9.52 (3/8)
7.5
Ø 9.52 (3/8)
7.5
Ø 9.52 (3/8)
7.5
Ø 9.52 (3/8)
7.5
Ø 9.52 (3/8)
7.5
Ø 9.52 (3/8)
7.5
Length A(m)
Liquid
Standard
Ø 6.35 (1/4)
7.5
Ø 9.52 (3/8)
7.5
Ø 9.52 (3/8)
7.5
Ø 9.52 (3/8)
7.5
Indoor unit
Elevation B(m)
Max.
Standard
Max.
20
5
20
5
30
5
50
5
50
5
85
5
85
5
85
5
85
5
Elevation B(m)
Max.
Standard
Max.
30
5
35
5
35
5
50
5
A
B
Indoor unit
Outdoor unit
Additional
refrigerant
(g/m)
15
20
15
20
30
20
30
35
30
40
30
40
30
40
30
40
30
40
Additional
refrigerant
(g/m)
30
20
30
35
30
35
30
40
Outdoor unit
A
B

Advertisement

Table of Contents
loading

This manual is also suitable for:

Uu37wrUu43wrUu48wrUu49wrUu42wrUu60wr ... Show all