INSTRUCTION MANUAL
ETHERNET INTERFACE MODULE
(Modbus/TCP, use with TR30)

BEFORE USE ....

Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System's Sales Office or representatives.
■ PACKAGE INCLUDES:
Network interface module ............................................ (1)
■ MODEL NO.
Confirm that the model number described on the product is
exactly what you ordered.
■ INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
POINTS OF CAUTION
■ CONFORMITY WITH EU DIRECTIVES
• The equipment must be mounted inside the instrument
panel of a metal enclosure.
• The actual installation environments such as panel con-
figurations, connected devices and connected wires may
affect the protection level of this unit when it is integrat-
ed in a panel system. The user may have to review the CE
requirements in regard to the whole system and employ
additional protective measures to ensure CE conformity.
■ POWER INPUT RATINGS
• Operational range & power consumption: Check the pow-
er rating for the unit on the specification label.
Rating 24V DC: 24V ±10%, approx. 12W
■ UNPLUGGING THE MODULE
• Before you remove the module from its base or mount it,
turn off the power supply for safety.
■ ENVIRONMENT
• Indoor use.
• When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -10 to +55°C
(14 to 131°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.
■ WIRING
• Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
• Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
■ AND ....
• The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.
INSTALLATION
Use the Installation Base Model R3-BSx, or Model R3-
BSWx for free I/O address capability.
Before mounting the Network Interface Module onto the
Base, be sure to configure the module as explained below.
■ DATA ALLOCATION
The setting determines the data area size assigned to each
I/O module mounted on the base.
The data sent/received via Modbus is mapped according to
this setting.
See "COMPONENT IDENTIFICATION."
■ NODE ADDRESS
See "COMPONENT IDENTIFICATION."
■ NETWORK SLOTS ON THE BASE
With Model R3-BSx base, mount the I/O Modules from the
left end (I/O 1) to the right in order that the Network Mod-
ule assigns data areas from I/O 1.
Network Module is mounted basically at the right end
though technically they could be mounted in any position.
With Model R3-BSWx base, there is no limitation in mount-
ing positions as I/O address can be assigned freely to each
module using rotary switches equipped on the base.
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
TR3EX
MODEL
I/O 1
I/O 2
I/O n
EM-8632
TR3EX
P. 1 / 7

Advertisement

loading

Summary of Contents for M-system TR3EX

  • Page 1: Before Use

    • The unit is designed to function as soon as power is sup- plied, however, a warm up for 10 minutes is required for Thank you for choosing M-System. Before use, please check satisfying complete performance described in the data contents of the package you received as outlined below.
  • Page 2: Component Identification

    SW2-7 SW2-8 SW SETTTING DATA ALLOCATION * Refer to the specifications of the related series for the Data Allocation Type of I/O modules. EM-8632 P. 2 / 7 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 3: Terminal Connections

    Applicable wire size: 0.75 – 1.25 mm 3 (.12) max. 4 min. (.16) 3.2 (.13) dia. 12 (.47) max. EM-8632 P. 3 / 7 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 4 Green in data sending. In normal operating conditions, these LEDs may seem to flash at once due to the high speed transmission. EM-8632 P. 4 / 7 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 5: Modbus I/O Assignments

    (Data Allocation Type) are allotted with the Data Allocation Type ‘1’ and ‘4’. With ‘8’ and ‘16’, 64 (4 × 16) are automatically assigned. EM-8632 P. 5 / 7 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 6 Lower 16 bits are allocated from the lowest address to higher ones, higher 16 bits in turn. 32-bit data cannot be accessed using floating addresses. Lower 16 bits Higher 16 bits EM-8632 P. 6 / 7 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 7 Input 16 (Output 16) 0 : OFF 1 : ON Regarding detailed data assignment of R3-RR8, refer to the instruction manual for R3-RR8 (EM-8432). EM-8632 P. 7 / 7 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...