Anti-Removal Tamper Option

The anti-removal option consists of two optional microswitches. To
mount this option, follow these steps:
1. Mount the first microswitch (an anti-removal tamper) onto the
bottom panel of the box, so that it presses against the wall.
2. Mount the second microswitch (an anti-opening tamper) so that
the lid of the box presses against it.
• In this configuration, there is no need to place the safety cover
on the RTU-A01P unit. The anti-opening tamper on the box
protects all the contents (the unit itself, the cables, and the
anti-removal tamper).
• If the box contains several RTU-A01P units, it is only necessary
to mount the anti-removal option on one of them.
3. Connect the anti-removal and the anti-opening tampers to their
respective jumpers (JP2 and JP3) on the RTU-A01P unit (see
Figure 9).
4. Connect the tampers so that they are left in the "open" position.
5. Use a Mascon CE100F24-2 Connector with AWG24 wires (no
polarity)
INSTALLATION
NOTES
J5
J4
J3
J2
ANTI-REMOVAL
TAMPER
JP2
ANTI-OPENING
TAMPER
JP3
SW1
Page 13