Network discharge air sensors

Advertisement

Quick Links

NS Series Network Discharge Air Sensors

Installation Instructions

NS-DTN7043-0, NS-DTN7043-2,
NS-DTN7083-0, NS-DTN7083-2
Applications
The NS Series Network Discharge Air Sensors are
electronic duct sensors designed to function directly
with Johnson Controls® digital controllers in HVAC
systems. Models in this series monitor the duct
temperature, typically at the discharge of the Variable
Air Volume (VAV) box, and transmit this data to the
controller Sensor Actuator (SA) Bus using the
305 cm (10 ft) wiring lead included with the unit. The
305 cm (10 ft) wiring lead consists of four
0.6 mm (22 AWG) diameter color-coded wires encased
in a plenum-rated jacket. Each of the wires is stripped
and tinned for easy connection to the SA Bus screw
terminal block.
The NS Series Network Discharge Air Sensors are
available with either a 102 or 203 mm (4 or 8 in.)
temperature probe. All models include DIP switches for
applications requiring multiple discharge air sensors,
each with a unique DIP switch address.
NS Series Network Discharge Air Sensors Installation Instructions
2 4 - 1 0 3 3 6 - 0 ,
IMPORTANT: The NS Series Network Discharge
Air Sensors are intended to provide an input to
equipment under normal operating conditions.
Where failure or malfunction of the discharge air
sensors could lead to personal injury or property
damage to the controlled equipment or other
property, additional precautions must be designed
into the control system. Incorporate and maintain
other devices, such as supervisory or alarm systems
or safety or limit controls, intended to warn of or
protect against failure or malfunction of the
discharge air sensors.
IMPORTANT : Le NS Series Network Discharge Air
Sensors est destiné à transmettre des données
entrantes à un équipement dans des conditions
normales de fonctionnement. Lorsqu'une défaillance
ou un dysfonctionnement du discharge air sensors
risque de provoquer des blessures ou
d'endommager l'équipement contrôlé ou un autre
équipement, la conception du système de contrôle
doit intégrer des dispositifs de protection
supplémentaires. Veiller dans ce cas à intégrer de
façon permanente d'autres dispositifs, tels que des
systèmes de supervision ou d'alarme, ou des
dispositifs de sécurité ou de limitation, ayant une
fonction d'avertissement ou de protection en cas de
défaillance ou de dysfonctionnement du discharge
air sensors.
1
R e v .
H
Part No. 24-10336-0, Rev. H
Issued February 2016

Advertisement

loading

Summary of Contents for Johnson Controls NS-DTN7043-2

  • Page 1: Installation Instructions

    IMPORTANT: The NS Series Network Discharge electronic duct sensors designed to function directly Air Sensors are intended to provide an input to with Johnson Controls® digital controllers in HVAC equipment under normal operating conditions. systems. Models in this series monitor the duct...
  • Page 2: North American Emissions Compliance

    North American Emissions Compliance Wiring If the NS Series Network Discharge Air Sensor is used United States in an application requiring multiple discharge air sensors, each with a unique DIP switch address, set This equipment has been tested and found to the DIP switches before wiring the unit.
  • Page 3: Repair Information

    If the NS Series Network Discharge Air Sensor fails to incorrectly. operate within its specifications, replace the unit. For a replacement discharge air sensor, contact the nearest Johnson Controls representative. NS Series Network Discharge Air Sensors Installation Instructions...
  • Page 4: Technical Specifications

    The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damage resulting from misapplication or misuse of its products.
  • Page 5 507 E. Michigan Street, Milwaukee, WI 53202 Metasys® and Johnson Controls® are registered trademarks of Johnson Controls, Inc. All other marks herein are the marks of their respective owners. © 2016 Johnson Controls, Inc. NS Series Network Discharge Air Sensors Installation Instructions Published in U.S.A.