MUA Filter Pressure Sensor
FPS Installation Guide
Open the access cover plate, by loosening the four screws and sliding the panel
sideways (use a flat blade (or hex) screwdriver).
Install the two screws from behind using two nuts (supplied) and tighten them
(see above, View A-A). DO NOT over-tighten.
Install the Pressure Sensor here by sliding the sensor over the screws.
Note: orientation of the pressure sensor, install so tubing can be inserted through
box wall to the sensor connections.
Secure the sensor using the two remaining nuts. DO NOT over-tighten.
Install 1/8" tubing (not included) between the V-Bank Filter Box and the Make-Up
Air Control Box.
*If the tubing does not fit snugly, heat up the ends and stretch them,
then slide them on while hot so they can set in place.
Check the following:
Orientation of the wiring to the sensor should be:
Yellow
White / Red / Black (heat shrink) Yellow
Route the other end of the harness to connect
to I2C Bus 1
Install the lid on to the Control Box and secure with
the screws.
If you removed the control panel mounting screws, reinstall them.
Access the MUA using a browser (see MUA-IOM) and perform the following:
In the browser at the end of the IP Address type: /config and hit enter.