6.18 Menu index card “Radio inputs – Dimming” ................... 50 6.19 Menu index card “Radio inputs – Venetian blind slow tilting” ............52 Technical data ..........................54 2011-2019, SOMFY Activites SA 50 avenue du Nouveau Monde 74300 Cluses France 2/55...
Page 3
Before starting up it is necessary to follow the safety instructions in these instructions. SOMFY cannot be held liable for defects and damages when these have been caused as a result of not following instructions (wrong installation, incorrect service etc.). Establishing, testing and starting up of the equipment is permitted only by a qualified person (in accordance with VDE 0100).
A manual command is a command which is generated by local conventional push buttons or by a Somfy RTS radio hand transmitter. A telegram which is sent on the objects 1-12 (bit commands) is also understood as a manual command.
2.1.1.1.1 Installation of the Motor Controller 4 AC WM 2.1.1.1.2 Din rail version 4 AC DRM Switch box Check range when using animeo RTS radio module! 2011-2019, SOMFY Activites SA 50 avenue du Nouveau Monde 74300 Cluses France 6/55...
The “US”-LED blinks regularly when the mains (230 V) and the KNX bus voltage are connected actively on the device. The device is ready for operation when the “US” LED blinks. 2011-2019, SOMFY Activites SA 50 avenue du Nouveau Monde 74300 Cluses France 7/55...
ETS was programmed, or after the device was unassigned by the ETS. The basic settings are overwritten by the settings in the ETS. 2011-2019, SOMFY Activites SA 50 avenue du Nouveau Monde 74300 Cluses France 8/55...
WM/DRM 220-230 V AC Selection of different user ergonomics Using the Reset/Prog button the press button user ergonomics for the local push button inputs or Somfy RTS radio hand transmitter can be determined. These settings are possible only in the delivery state, be- fore the device is programmed with ETS software or after the device is unassigned with the ETS.
H Alternatively to the conventional push buttons, the settings can also be done using the Somfy RTS Trans- mitter and animeo RTS Radio Module (ref. 1860105). A setting using animeo KNX RTS Receiver (ref.
Rest/Prog button. Over the function “Unload” in the ETS, all settings of the device can be set back in the delivery state. The Reset/Prog button is then freed again. 2011-2019, SOMFY Activites SA 50 avenue du Nouveau Monde 74300 Cluses France 11/55...
Motor 3 Slat position 1 Byte 5.001 defined by the received value. If a Venetian blind 2011-2019, SOMFY Activites SA 50 avenue du Nouveau Monde 74300 Cluses France 12/55...
Page 13
Motor 3 Security, low prio 1 bit 1.001 the ETS parameters (Security, low prio) and any 2011-2019, SOMFY Activites SA 50 avenue du Nouveau Monde 74300 Cluses France 13/55...
Page 14
“0”, the blind moves to the posi- tion it was, before any security was activated. 2011-2019, SOMFY Activites SA 50 avenue du Nouveau Monde 74300 Cluses France 14/55...
Page 15
If a telegram with the value “0” is received on one Motor 3 IP1 Save/Delete 1 bit 1.002 of these communication objects the IP1 is deleted. 2011-2019, SOMFY Activites SA 50 avenue du Nouveau Monde 74300 Cluses France 15/55...
Page 16
“0” is sent. The upper and lower end position is de- termined by the parameterized move times. 2011-2019, SOMFY Activites SA 50 avenue du Nouveau Monde 74300 Cluses France 16/55...
Page 17
When releasing the corresponding switch at the input B, a stop com- mand is generated. The last activated dimming step becomes inverted. 2011-2019, SOMFY Activites SA 50 avenue du Nouveau Monde 74300 Cluses France 17/55...
Page 18
If the Venetian blind is in a fully moving process with a short pressing of “DOWN” button at channel 1 learned in remote a stop or- der is generated. 2011-2019, SOMFY Activites SA 50 avenue du Nouveau Monde 74300 Cluses France 18/55...
Page 19
100 %. When releasing the appropriate switch at the input B a stop order is generated. The dim- ming action operated last is thus inverted. 2011-2019, SOMFY Activites SA 50 avenue du Nouveau Monde 74300 Cluses France 19/55...
Page 20
1 165 Radio Input 4: 8-Bit value “DOWN” 1 Byte 5.010 see description of object 135, channel 4 instead button of channel 1 2011-2019, SOMFY Activites SA 50 avenue du Nouveau Monde 74300 Cluses France 20/55...
Page 21
1 177 Radio Input 5: Dimming/slow tilting 4 Bit 3.007 see description of object 137, channel 5 instead 3.008 of channel 1 2011-2019, SOMFY Activites SA 50 avenue du Nouveau Monde 74300 Cluses France 21/55...
Yes With the parameter “Yes” the settings for the priority functions become visible. At the same time the neces- sary objects appear. 2011-2019, SOMFY Activites SA 50 avenue du Nouveau Monde 74300 Cluses France 22/55...
Page 23
Over the corresponding object (56-59), switching to and from priority manual function and priority auto- matic function can be done at any time. H See chapter 1 Definitions. 2011-2019, SOMFY Activites SA 50 avenue du Nouveau Monde 74300 Cluses France 23/55...
Page 24
If the value „100“ is transmitted to the corresponding object (17–20), the slats are turned or opened at maximum. 2011-2019, SOMFY Activites SA 50 avenue du Nouveau Monde 74300 Cluses France 24/55...
With this parameter it is determined that the corresponding blind is selected over move/stop commands when the controlling is done over the local push button inputs or via the Somfy RTS radio hand transmitter. 2011-2019, SOMFY Activites SA 50 avenue du Nouveau Monde 74300 Cluses France...
Page 26
With this parameter it is determined that the corresponding window is selected over move/stop commands when the controlling is done over the local push button inputs or via the Somfy RTS radio hand transmitter. When the local push button inputs are used as universal push button inputs, the operating ergonomics are defined over the corresponding parameters (short/long pressing of the push button).
Page 27
(value “0”) is also inactive, the blind moves again to the last position with the last angle before activating the high and low priorities. 2011-2019, SOMFY Activites SA 50 avenue du Nouveau Monde 74300 Cluses France 27/55...
If the IP UP/Down position parameter is set to 0 %, the IP position is disabled. This function avoids any movement of the blinds by using the “my” or IP push button. 2011-2019, SOMFY Activites SA 50 avenue du Nouveau Monde 74300 Cluses France 28/55...
Page 29
With this parameter the intermediate position 2 “Slats” is defined. The set value in % refers to the parameter- ized complete slats turn of the corresponding Venetian blind of the menu index card Motor 1…4/Motor 1-4. 2011-2019, SOMFY Activites SA 50 avenue du Nouveau Monde 74300 Cluses France 29/55...
Page 30
Only after completion any further commands are blocked which are gen- erated via local push button inputs or Somfy RTS radio signals. If a telegram with the value “0” is received on the corresponding object, the local push button inputs and Somfy RTS radio signals are freed again.
1…4 is Venetian blind Up/Down. Menu index card “Binary inputs - Venetian blind Up/Down” 6.5.1 Basic Function Venetian blinds Up/Down Selected option: 2011-2019, SOMFY Activites SA 50 avenue du Nouveau Monde 74300 Cluses France 31/55...
Normally closed: The contact at the local input is activated opened and not activated closed. Menu index card “Binary inputs – Switch/Dry contact” 6.6.1 Basic Function Selected option: Switch dry contact 2011-2019, SOMFY Activites SA 50 avenue du Nouveau Monde 74300 Cluses France 32/55...
Page 33
If a rising or falling flank at the local input appears, this is not evaluated. 6.6.3 Edge evaluation contact B For detailed information see Edge evaluation contact A. 2011-2019, SOMFY Activites SA 50 avenue du Nouveau Monde 74300 Cluses France 33/55...
Page 34
With this parameter the time intervals are defined in which the corresponding object value should be trans- mitted cyclically. H Please beware that cyclical supervision time of the receiver is approximately 4 times higher than that of the transmitter. 2011-2019, SOMFY Activites SA 50 avenue du Nouveau Monde 74300 Cluses France 34/55...
0 – 255 Selection options: With this parameter the value is set which is transmitted with a rising edge at the local input B. 2011-2019, SOMFY Activites SA 50 avenue du Nouveau Monde 74300 Cluses France 35/55...
Default value: On/Off Selection options: Toggle/Toggle This parameter defines the value which is transmitted with a short pressing of the corresponding input. 2011-2019, SOMFY Activites SA 50 avenue du Nouveau Monde 74300 Cluses France 36/55...
Page 37
(4 bit). When the corresponding push button at the local input A or B is released, a stop command is generated. 2011-2019, SOMFY Activites SA 50 avenue du Nouveau Monde 74300 Cluses France 37/55...
Page 38
“interval of 0.5 seconds” is set, then with a longer pressing of the push button on the corresponding local in- put, every 0.5 seconds ¼ brighter or darker will be dimmed. 2011-2019, SOMFY Activites SA 50 avenue du Nouveau Monde 74300 Cluses France 38/55...
100 telegrams per 17 sec. 127 telegrams per 17 sec. This parameter defines the number of the telegrams which can be transmitted within 17 seconds. 2011-2019, SOMFY Activites SA 50 avenue du Nouveau Monde 74300 Cluses France 39/55...
If electronic motors are controlled using this Motor Controller, it is imperative to set the start delay time of the electronic motor in the settings of the Motor Controller. 2011-2019, SOMFY Activites SA 50 avenue du Nouveau Monde 74300 Cluses France 40/55...
Intermediate position 2 (IP 2) Close window Open window This parameter defines the position which is moved to with a bus power failure. 2011-2019, SOMFY Activites SA 50 avenue du Nouveau Monde 74300 Cluses France 41/55...
Page 42
“Reaction with bus voltage return” and “Reaction with mains voltage return (230 V)”. H Advantage: Power spikes can thus be reduced in larger projects. 2011-2019, SOMFY Activites SA 50 avenue du Nouveau Monde 74300 Cluses France 42/55...
If this parameter is selected, the corresponding upper or lower end position is announced on the bus for each blind individually. Here, the objects in each case (81-84) and (91-94) are made available. 2011-2019, SOMFY Activites SA 50 avenue du Nouveau Monde 74300 Cluses France 43/55...
Page 44
• Cyclic This parameter opens a further parameter (“Every”) with which the time for cyclical sending is set. 2011-2019, SOMFY Activites SA 50 avenue du Nouveau Monde 74300 Cluses France 44/55...
1 (channel A) and are identical for the radio inputs 2 - 5 (channel B, C, D and E). 2011-2019, SOMFY Activites SA 50 avenue du Nouveau Monde 74300 Cluses France 45/55...
If the “my” button in the radio transmitter is pressed, no object is generated. H See chapter 1 Definitions for On (“1”) Off (“0”) Toggle (“1/0”). 2011-2019, SOMFY Activites SA 50 avenue du Nouveau Monde 74300 Cluses France 46/55...
If the “Up” button in the radio transmitter is pressed, no object is generated. H See chapter 1 Definitions for On (“1”) Off (“0”) Toggle (“1/0”). 2011-2019, SOMFY Activites SA 50 avenue du Nouveau Monde 74300 Cluses France 47/55...
Page 48
Selection options: With this parameter the value (0 – 255) is set which is transmitted while pressing the “my” button in the radio transmitter. 2011-2019, SOMFY Activites SA 50 avenue du Nouveau Monde 74300 Cluses France 48/55...
If the “my” button in the radio transmitter is pressed, the object value “On” is generated. The duration of the activity is not evaluated. 2011-2019, SOMFY Activites SA 50 avenue du Nouveau Monde 74300 Cluses France 49/55...
(Brighter/darker dimming). If the time, for example, is set at 0.5 seconds, a long-term telegram is generated after a longer pressing than 0.5 seconds. With a pressing duration which is shorter than 0.5 seconds, a short-term telegram is generated. 2011-2019, SOMFY Activites SA 50 avenue du Nouveau Monde 74300 Cluses France 50/55...
Page 51
With this parameter the value (0 – 255) is set which is transmitted while pressing the “my” button in the radio transmitter. 6.18.4.3 No function If the “my” button in the radio transmitter is pressed, no object is generated. 2011-2019, SOMFY Activites SA 50 avenue du Nouveau Monde 74300 Cluses France 51/55...
6.19.4 Functionality of my push button No function Default value: 1-Bit value Selection options: 8-Bit value No function 2011-2019, SOMFY Activites SA 50 avenue du Nouveau Monde 74300 Cluses France 52/55...
Page 53
With this parameter the value (0 – 255) is set which is transmitted while pressing the “my” button in the radio transmitter. 6.19.4.3 No function If the “my” button in the radio transmitter is pressed, no object is generated. 2011-2019, SOMFY Activites SA 50 avenue du Nouveau Monde 74300 Cluses France 53/55...
Method of attachment for non-detachable cords: Screwless spring terminal EMC emission test: = 230 V AC I = 0,5 A (EN 55022 Class B emission) 2011-2019, SOMFY Activites SA 50 avenue du Nouveau Monde 74300 Cluses France 54/55...
Page 55
KNX 4 AC Motor Controller 30.01.2019 WM/DRM 220-230 V AC 2011-2019, SOMFY Activites SA 50 avenue du Nouveau Monde 74300 Cluses France 55/55...
Need help?
Do you have a question about the animeo 1860114 and is the answer not in the manual?
Questions and answers