INTRODUCTION Thank you for choosing our product. The accessories described in this manual are of the highest quality, carefully designed and built in order to ensure excellent performance. This manual contains detailed instructions on how to install and use the product. This manual must be stored in a safe place and CONSULTED BEFORE USING THE DEVICE for proper usage instructions as well as maximum performance from the device itself.
Page 4
INDEX PRESENTATION N THE BOX XTERNAL VIEW PROFIBUS DP GATEWAY CONNECTORS AND LEDS PROFIBUS CONNECTOR OWER CONNECTOR ULTI CONNECTOR TATUS MULTICOM 302 JUMPER AND DIP SWITCHES SETTINGS INSTALLATION PROFIBUS CONFIGURATION SWITCHES ↔ PROFIBUS ONNECTION CABLE ULTI ATEWAY DIN‐ RAIL MOUNTING PROFIBUS I/O DATA - 4 -...
PRESENTATION MultiCOM 411 is a complete PROFIBUS-DP slave according to IEC 61158. It allows to integrate the management and monitoring of the UPS into a PROFIBUS network. Baud rates from 9.6 kbit/s up to 12 Mbit/s are supported and automatically detected.
PROFIBUS DP GATEWAY CONNECTORS AND LEDS PROFIBUS CONNECTOR Signal Description Housing Shield Bus cable shield, connected to PE 1, 2, 7, 9 B-Line Positive RxD/TxD (RS485) Request To Send GNDBUS Isolated GND from RS-485 side (female) +5V BUS Isolated +5 V output from RS-485 side (80 mA max) A-Line Negative RxD/TxD (RS485) May be used by some devices to determine the direction of transmission...
MULTICOM 302 JUMPER AND DIP SWITCHES SETTINGS INSTALLATION Remove the cover of the UPS expansion slot by removing the two retaining screws. Insert MultiCOM 302 in the slot. Fix the cover provided using the screws previously removed. Connect the PROFIBUS DP Gateway to the MultiCOM 302 using the cable provided with the device. NOTE: if necessary, you can also use another cable realized in accordance with the specifications (see Connection cable MultiCOM 302 ↔...
PROFIBUS CONFIGURATION SWITCHES The configuration switches are used to set the PROFIBUS node address. Remove the plastic hatch to configure the switches (see image below). Note that the node address cannot be changed during runtime, i.e. the gateway requires a reset for changes to have effect.
PROFIBUS I/O DATA The UPS’s values are presented to the Master PLC/Controller as easily processed I/O data. INPUT DATA BYTE # REGISTER # DESCRIPTION UNIT High States / alarms 1 States / alarms 2 Charge% Autonomy Minutes RESERVED Load phase L1 Load phase L2 Load phase L3 Input voltage (Ph-N) V1 Input voltage (Ph-N) V2...
Page 10
INPUT DATA BYTE # REGISTER # DESCRIPTION UNIT High RESERVED Battery temperature °C Power 1 temperature °C Power 2 temperature °C Power 3 temperature °C Input current phase L1 A/10 Input current phase L2 A/10 Input current phase L3 A/10 RESERVED RESERVED RESERVED...
STATES / ALARMS 2 BIT # DESCRIPTION 15 (MSB) UPS failure [0=NO / 1=YES] Alarm overload [0=NO / 1=YES] Alarm temperature [0=NO / 1=YES] Input mains present [0=NO / 1=YES] 0 (LSB) OUTPUT DATA BYTE # REGISTER # DESCRIPTION UNIT High Command Code: 0 (0x0000) →...
Page 12
Example of master configuration to have accesso to UPS state and commands Example of master configuration to have accesso to all UPS measurements and commands Example of master configuration to have access to the UPS input data register from n°1 to n°16 - 12 -...