All the components are supplied in particular hardware and software configurations appropriate for the application. Modifications to hardware or software configurations other than those described in the documentation are not permitted, and nullify the liability of Beckhoff Automation GmbH & Co. KG. Personnel qualification This description is only intended for trained specialists in control, automation and drive engineering who are familiar with the applicable national standards.
FF - firmware version (not applicable for digital modules) HH - hardware version Example with ser. no.: 35 05 00 01: 35 - week of production 35 05 - year of production 2005 00 - firmware version 00 01 - hardware version 01 KM2604 and KM2614 Version: 2.1.0...
Terminal reliably meets increased requirements for I/O signals through its modularity and compact design. The existing Beckhoff Bus Terminal system is complemented by the new version of the EMxxxx / KMxxxx Terminal Module with increased packing density. In many areas of application, cost benefits can be realized through lower overall installed size and application-specific signal mix.
The Terminal Modules combine 16, 32 or 64 digital inputs or outputs on a very small area. This compact and slimline design enables very high packing densities, leading to smaller control cabinets and terminal boxes. KM2604 and KM2614 Version: 2.1.0...
Product overview Four-channel relay module, 230 V , 16 A The KM2604 and KM2614 terminal module combines 4 pluggable power relays (ZB2601 or ZB2602) in one fieldbus module. The high switching capacity of 16 A at 230 V enables direct mains connection of consumers with high current consumption.
Permissible ambient temperature range during operation 0°C ... + 55°C Permissible ambient temperature range during storage -25°C ... + 85°C Permissible relative air humidity 95 %, no condensation Mounting on relay base with on relay socket reteiner bracket Approval KM2604 and KM2614 Version: 2.1.0...
Attention An overall width of 80 cm must not be exceeded! Also ensure that the current consumption of the Bus Terminals/terminal modules from the K-bus does not overload the K-bus power supply of the Bus Coupler. Version: 2.1.0 KM2604 and KM2614...
• Lever the unlatching hook on the left-hand side of the terminal module upwards with a screwdriver (3). As you do this ◦ an internal mechanism pulls the two latching lugs (3a) from the top hat rail back into the terminal module, ◦ the unlatching hook moves forwards (3b) and engages KM2604 and KM2614 Version: 2.1.0...
Page 16
• In the case 32 and 64 channel terminal modules (KMxxx4 and KMxxx8 or EMxxx4 and EMxxx8) you now lever the second unlatching hook on the right-hand side of the terminal module upwards in the same way. • Pull (4) the terminal module away from the mounting surface. Version: 2.1.0 KM2604 and KM2614...
Mounting and wiring Connection Fig. 11: Connection KM2604 Power supply for the relays Terminal point Comment 24 V 24 V supply for relays 24 V 24 V 0 V 0 V supply for relays 0 V 0 V Connecting the relays Terminal point no. Output/relay Relay connection KM2604 and KM2614...
Beckhoff's branch offices and representatives Please contact your Beckhoff branch office or representative for local support and service on Beckhoff products! The addresses of Beckhoff's branch offices and representatives round the world can be found on her internet pages: http://www.beckhoff.com You will also find further documentation for Beckhoff components there.
Page 19
Terminal module with 16 channels ....................Fig. 6 Terminal module with 32 channels ....................Fig. 7 Terminal module with 64 channels ....................Fig. 8 KM2604 ............................Fig. 9 KM2614 ............................Fig. 10 Dimensions ..........................Fig. 11 Connection KM2604 ........................KM2604 and KM2614 Version: 2.1.0...