APPENDIX A2
A2.1 WILO-PARA 25-130/7-50/SC-
6#GRA CIRCULATING PUMP
A2.1.1 PUMP SPECIFICATION
Table A2-1: Pump specification
Make and model
Construction
Pump housing
Impellar
Pump shaft
Bearing
Motor Data
Speed
Power consumption @ 1 - 230V
Current @ 1 - 230V
Minimum starting voltage
Minimum running voltage
Peak inrush current
Starting torque
Electrical
Mains connection
Protection Class
Insulation Class
Motor Protection
Performance
Max. delivery head
Max. volume flow
Minimum suction head @ 50/95°C
Energy Efficiency Index (EEI)
Settings
Application
Maximum Static Pressure
Fluid Temperature range @
maximum ambient temperatures
(See Section A2.1.2)
Approved Fluids
Page 60
WILO-PARA 25-130/7-50/SC-6#GRA
CIRCULATING PUMP
Wilo - PARA 25-130/7- 50/SC-
6#GRA
Cast iron (with cataphoresis
treatment)
PP composite with GF 40%
Stainless Steel
Carbon, metal impregnated
2580 - 4700rpm
8.2 - 50W
0.07 - 0.43A
170V
160V
>3A
>25N.cm
1ph 230V AC +10%/-15% 50/60Hz
IPx4D
F
Integrated
7.7m @ Q = 0 m
/h
3
3.5 m
/h
3
0.5/4.5m
≤ 0.20
∆P-variable (1-7m head)
∆P-constant (1-7m head)
Constant Speed (I, II and III)
PN10
Maximum ambient temperature
58°C: 0 to 100°C
Maximum ambient temperature
62°C: 0 to 90°C
Maximum ambient temperature
66°C: 0 to 80°C
Maximum ambient temperature
71°C: 0 to 70°C
Heating Water
Water/Glycol - Max 1:1 (above 20%
check pumping data)
A2.1.2 THERMAL PROTECTION FUNCTION
The pump is equipped with a thermal self-protection mode.
If the fluid temperature exceeds the maximum value at a specific
ambient temperature, e.g. 90°C at an ambient of 62°C, the pump
will automatically reduce the power consumption, reducing the
speed and performance of the pump.
In this condition the Run/Fault signal LED will be blinking RED.
When normal temperature conditions return the pump will
automatically revert to normal operation.
If the fluid temperature increases further, the thermal protection
function may stop the pump temporarily.
In this condition the Run/Fault signal LED on the pump will be
constant RED until normal temperature conditions return.
A2.1.3 PUMP COMPONENTS
5
4
3
2
1
Figure A2-1: Pump components and control panel
1.
Pump housing
2.
Glandless motor
3.
Condensate drain openings
(4 around motor)
4.
Housing screws
5.
Control module
A2.1.4 CONTROL PANEL
Indicator LEDs
Run/Fault signal LED (item 8, Figure A2-1)
-
LED is GREEN when pump is running in normal pump
operation.
-
LED lights up RED/flashes when there is a fault (refer to
Section A2.2).
Control mode display LEDs (item 9, Figure A2-1)
Pump curve display LEDs (item 10, Figure A2-1)
LED combinations are used to indicate when the following
functions are in operation:
-
Pump venting (refer to Sections A2.1.5 and A2.1.6 for
information on how to activate this function).
-
Manual restart (refer to Sections A2.1.5 and A2.2 for
information on how to activate this function).
-
Key lock (refer to Sections A2.1.5 and A2.1.6 for
information on how to activate this function).
Appendix A2: Wilo-PARA 25-130/7-50/SC-6#GRA
8
9
6
7
10
6.
Rating plate
7.
Operating button for pump
adjustment
8.
Run/Fault signal LED
9.
Display of selected control
mode
10. Display of selected pump
curve (I, II, III)