[English]). For start-up instructions, see chapter EN – Quick start-up guide on page To read a manual, go to www.abb.com/drives/documents and search for the document number. Obey the safety instructions WARNING! Obey these instructions. If you ignore them, injury or death, or damage to the equipment can occur: •...
26 EN – R6…R9 Quick installation guide For information on reforming the capacitors, see Converter module capacitor reforming instructions (3BFE64059629 [English]), available on the Internet at www.abb.com/drives/documents. Select the power cables Size the power cables according to local regulations to carry the nominal current given on the type designation label of your drive.
Measure the insulation resistance between each phase conductor and then between each phase conductor and the Protective Earth conductor using a measuring voltage of 1000 V DC. The insulation resistance of an ABB motor must exceed 100 Mohm (reference value at 25 °C or 77 °F). For the insulation resistance of other motors, see the manufacturer’s instructions.
Page 28
28 EN – R6…R9 Quick installation guide WARNING! Do not install the drive with the ground-to-phase varistor connected on an IT system (an ungrounded power system or a high-resistance-grounded [over 30 ohms] power system), otherwise the varistor circuit can be damaged. Check from the table below if you have to disconnect the EMC filter (EMC) or ground- to-phase varistor (VAR).
EN – R6…R9 Quick installation guide 29 Disconnect EMC filter or ground-to-phase varistor, if needed To disconnect the internal EMC filter or ground-to-phase varistor, if needed, do as follows: 1. Switch off the power from the drive. 2. Open the front cover, if not already opened, see steps 5, IP21 and 5, IP55 in figure R6…R9 Figures A on page...
30 EN – R6…R9 Quick installation guide Connect the power cables See figure on page 45. Use symmetrical shielded cable for motor cabling. If the cable shield is the sole PE conductor for drive or motor, make sure that is has sufficient conductivity for the PE.
46. It shows an example with one analog signal cable and one digital signal cable. Make the connections according to the macro in use. The default connections of the ABB standard macro are shown in section Default I/O connections on page 32.
32 EN – R6…R9 Quick installation guide Default I/O connections Default I/O connections of the ABB Standard macro are shown below. AI1 U/I Voltage/Current selection for AI1: AI2 U/I Voltage/Current selection for AI2: Reference voltage and analog inputs and outputs Signal cable shield (screen) Output frequency/speed reference: 0…10 V...
EN – R6…R9 Quick installation guide 33 Install optional modules, if any See chapter Electrical installation in ACS580-01 (0.75 to 250 kW) hardware manual (3AXD50000018826 [English]). Install side plates and covers See figure R6…R9 Figures E on page 47. IP21 1.
EN – Quick start-up guide 35 EN – Quick start-up guide This guide describes how to start-up the drive using the First start assistant on the assistant control panel. Before you start Ensure that the drive has been installed as described in chapter EN –...
Page 36
36 EN – Quick start-up guide The First start assistant guides you through the first start-up. The assistant begins automatically. Wait until the control panel enters the view shown on the right. Select the language you want to use by highlighting it (if not already highlighted) and pressing (OK).
Page 37
Refer to the motor nameplate for the following nominal value settings of the motor. Enter the values exactly as shown on the motor nameplate. Example of a nameplate of an induction (asynchronous) motor: ABB Motors motor M2AA 200 MLA 4 IEC 200 M/L 55 Ins.cl.
Page 38
38 EN – Quick start-up guide Check that the motor data is correct. Values are predefined on the basis of the drive size but you should verify that they correspond to the motor. Start with the motor type. Motor nominal cosΦ and nominal torque are optional.
Page 39
EN – Quick start-up guide 39 The first start is now complete and the drive is ready for use. Press (Done) to enter the Home view. The Home view monitoring the values of the selected signals is shown on the panel. 2 –...
Page 40
40 EN – Quick start-up guide 2 – Additional settings: Start, stop and reference values If you do not wish to use a macro, define the settings for start, stop and reference: Select Start, stop, reference and press (Select) (or Adjust the parameters according to your needs.
Page 41
EN – Quick start-up guide 41 2 – Additional settings: Limits Select Limits and press (Select) (or Adjust the parameters according to your needs. Select a parameter and press (Edit). After making the adjustments, go back to the Primary settings menu by pressing (Back).