Intra-Sewi KNX TH-Pr
Ambient Climate Sensor with Presence Detector
Item numbers 70662 (white), 70667 (black)
Installation and Ad justment

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 70662 and is the answer not in the manual?

Questions and answers

Summary of Contents for KNX 70662

  • Page 1 Intra-Sewi KNX TH-Pr Ambient Climate Sensor with Presence Detector Item numbers 70662 (white), 70667 (black) Installation and Ad justment...
  • Page 3: Table Of Contents

    5.6.2. Heating control level 1/2 ................38 5.6.3. Cooling control level 1/2 ................41 5.7. Humidity Measurement ..................43 Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany Sensor Intra-Sewi KNX TH-Pr • from version 1.0 Version: 11.06.2018 • Technical changes and errors excepted.
  • Page 4 5.15.AND logic connection inputs ................56 5.15.1. Connection inputs of the OR logic ............. 58 Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany Sensor Intra-Sewi KNX TH-Pr • from version 1.0 Version: 11.06.2018 • Technical changes and errors excepted.
  • Page 5 Clarification of signs Installation, inspection, commissioning and troubleshooting of the device must only be carried out by a competent electrician. This manual is amended periodically and will be brought into line with new software releases. The change status (software version and date) can be found in the contents footer. If you have a device with a later software version, please check www.elsner-elektronik.de in the menu area "Service"...
  • Page 6 Clarification of signs...
  • Page 7: Description

    2 actuation variable comparators to output minimum, maximum or average values. 5 inputs each for values received via communication objects Configuration is made using the KNX software ETS. The product file can be down- loaded from the Elsner Elektronik website on www.elsner-elektronik.de in the “Ser- vice”...
  • Page 8: Technical Data

    100° × 82° (see also Coverage area of the motion detector) Range approx. 5 m The product is compliant with the provisions of the EU guidelines. Sensor Intra-Sewi KNX TH-Pr • Version: 11.06.2018 • Technical changes and errors excepted.
  • Page 9: Measuring Accuracy

    Elsner Elektronik is not liable for any changes in norms and standards which may occur after publication of these operating instructions. 2.2. Installation location Install and use only in dry interior rooms! Avoid condensation. Sensor Intra-Sewi KNX TH-Pr • Version: 11.06.2018 • Technical changes and errors excepted.
  • Page 10: Coverage Area Of The Motion Detector

    Installation and start-up The Sensor Intra-Sewi KNX TH-Pr is installed in a false ceiling or a standard con- nection socket (Ø 60 mm, 42 mm deep). The device must be installed on the ceiling, so that the movement capturing takes place from above.
  • Page 11: Installation Of The Sensor

    Place the device in the installation opening in the ceiling. For this, fold the clamps up- wards and guide the device through the installation opening with the clamps first. Intra-Sewi KNX TH-Pr is automatically fixed by the clamps. Sensor Intra-Sewi KNX TH-Pr • Version: 11.06.2018 • Technical changes and errors excepted.
  • Page 12: Installation In Connector Socket

    Connect the bus line to the KNX terminal (red/black). Clamp the device in the support ring so that the springs on the device snap over the tabs of the support ring. Fig. 4: Tragring Tabs Sensor Intra-Sewi KNX TH-Pr • Version: 11.06.2018 • Technical changes and errors excepted.
  • Page 13: Back View: Connection

    The connection is made with the KNX terminal (red/black) to KNX TP. Fig. 6 Clamps for installation in false ceiling Springs for installation in sup- port ring KNX terminal Sensor Intra-Sewi KNX TH-Pr • Version: 11.06.2018 • Technical changes and errors excepted.
  • Page 14: Front View: Programming And Addressing

    The movement sensor and the airing lamella must not get dirty or covered. As a rule, it is sufficient to wipe the device with a soft, dry cloth twice a year. Sensor Intra-Sewi KNX TH-Pr • Version: 11.06.2018 • Technical changes and errors excepted.
  • Page 15: Transfer Protocol

    4 Bytes Motion sensor: Master 1: Switch Input RWC- [7.5] 2 Bytes on delay DPT_TimePeriodSec Motion sensor: Master 1: Switch Input RWC- [7.5] 2 Bytes off delay DPT_TimePeriodSec Sensor Intra-Sewi KNX TH-Pr • Version: 11.06.2018 • Technical changes and errors excepted.
  • Page 16 4 Bytes Motion sensor: Master 3: Switch Input RWC- [7.5] 2 Bytes on delay DPT_TimePeriodSec Motion sensor: Master 3: Switch Input RWC- [7.5] 2 Bytes off delay DPT_TimePeriodSec Sensor Intra-Sewi KNX TH-Pr • Version: 11.06.2018 • Technical changes and errors excepted.
  • Page 17 1 Bit value min./max. query DPT_Trigger Temperature sensor: measured Output R-CT [9.1] 2 Bytes value minimum DPT_Value_Temp Temperature sensor: measured Output R-CT [9.1] 2 Bytes value maximum DPT_Value_Temp Sensor Intra-Sewi KNX TH-Pr • Version: 11.06.2018 • Technical changes and errors excepted.
  • Page 18 Temp. threshold value 4: (1:+ | Input -WC- [1.1] 1 Bit 0:-) DPT_Switch Temp. thresh. val. 4: Switching Input -WC- [7.5] 2 Bytes delay from 0 to 1 DPT_TimePeriodSec Sensor Intra-Sewi KNX TH-Pr • Version: 11.06.2018 • Technical changes and errors excepted.
  • Page 19 112 Temp.control: Setpoint Eco coo- Input / -WCT [9.1] 2 Bytes ling Output DPT_Value_Temp 113 Temp.control: Setpoint Eco coo- Input -WC- [1.1] 1 Bit ling (1:+ | 0:-) DPT_Switch Sensor Intra-Sewi KNX TH-Pr • Version: 11.06.2018 • Technical changes and errors excepted.
  • Page 20 139 Humidity thresholdV 1: (1:+ | 0:-) Input -WC- [1.1] 1 Bit DPT_Switch 140 Humidity thresholdV 1: Delay Input -WC- [7.5] 2 Bytes from 0 to 1 DPT_TimePeriodSec Sensor Intra-Sewi KNX TH-Pr • Version: 11.06.2018 • Technical changes and errors excepted.
  • Page 21 161 Humidity thresholdV 4: Swit- Input -WC- [1.1] 1 Bit ching output block DPT_Switch 165 Humidity control: Block (1: bloc- Input -WC- [1.2] 1 Bit king) DPT_Bool Sensor Intra-Sewi KNX TH-Pr • Version: 11.06.2018 • Technical changes and errors excepted.
  • Page 22 1 Bit fortable|0=uncomfort. DPT_Switch 187 Ambient climate status: Text Output R-CT [16.0] 14 Bytes DPT_String_ASCII 189 Actuating variable comparator Input -WC- [5.1] 1 Byte 1: Input 1 DPT_Scaling Sensor Intra-Sewi KNX TH-Pr • Version: 11.06.2018 • Technical changes and errors excepted.
  • Page 23 210 Logic input 7 Input -WC- [1.2] 1 Bit DPT_Bool 211 Logic input 8 Input -WC- [1.2] 1 Bit DPT_Bool 212 Logic input 9 Input -WC- [1.2] 1 Bit DPT_Bool Sensor Intra-Sewi KNX TH-Pr • Version: 11.06.2018 • Technical changes and errors excepted.
  • Page 24 R-CT [5.010] DPT_- 1 Bit - Value_1_Ucount 2x1 Byte 234 AND logic 4: 8 bit output B Output R-CT [5.010] DPT_- 1 Bit - Value_1_Ucount 2x1 Byte Sensor Intra-Sewi KNX TH-Pr • Version: 11.06.2018 • Technical changes and errors excepted.
  • Page 25 250 OR logic 4: 8 bit output B Output R-CT [5.010] DPT_- 1 Bit - Value_1_Ucount 2x1 Byte 251 OR logic 4: Block Input -WC- [1.1] 1 Bit DPT_Switch Sensor Intra-Sewi KNX TH-Pr • Version: 11.06.2018 • Technical changes and errors excepted.
  • Page 26: Parameter Setting

    • at value 1: release | at value 0: block • at value 0: release | at value 1: block Value prior to first communication 0 • 1 Sensor Intra-Sewi KNX TH-Pr • Version: 11.06.2018 • Technical changes and errors excepted.
  • Page 27 Cycle reset object type • 1 bit • 1 byte (0%...100%) Cycle reset at value 0 • 1 and/or 0...100; 1 Sensor Intra-Sewi KNX TH-Pr • Version: 11.06.2018 • Technical changes and errors excepted.
  • Page 28: Master 1/2/3/4

    Then specify the switch-on and switch-off values (brightness range). The switch-on value is the value, below which the room should be lit in the event of Sensor Intra-Sewi KNX TH-Pr • Version: 11.06.2018 • Technical changes and errors excepted.
  • Page 29 Settings for all types of motion detection: The following settings can be made, independent of the motion detection type, i.e. for "constant" and "brightness dependent" motion recognition. Sensor Intra-Sewi KNX TH-Pr • Version: 11.06.2018 • Technical changes and errors excepted.
  • Page 30 In addition, you can refer to a slave signal, i.e. a signal from an additional motion de- tector, for controlling purposes. Use slave signal No • Yes Sensor Intra-Sewi KNX TH-Pr • Version: 11.06.2018 • Technical changes and errors excepted.
  • Page 31: Align Communication Between Master And Slave

    "slave: cycle reset" in order to immediately send a message to the bus in the event of a motion detection. The master receives the motion message without having to wait for the next slave transmission cycle. Sensor Intra-Sewi KNX TH-Pr • Version: 11.06.2018 • Technical changes and errors excepted.
  • Page 32: Temperature Measurement

    "Reset temperature min/max. value" objects to reset the values to the current readings. The values are not retained after a reset. Use minimum and maximum value No • Yes Sensor Intra-Sewi KNX TH-Pr • Version: 11.06.2018 • Technical changes and errors excepted.
  • Page 33: Temperature Pi Control

    The comfort object blocks the eco/standby object, and the frost/ heat protection object has the highest priority. Objects „... Mode (1: Eco, 0: Standby)“, „... comfort activation mode" and „... frost/heat protection activation mode" Sensor Intra-Sewi KNX TH-Pr • Version: 11.06.2018 • Technical changes and errors excepted.
  • Page 34 • Dual-level heating • Single-level cooling • Dual-level cooling • Single-level heating + single-level cooling • Dual-level heating + single-level cooling • Dual-level heating + dual-level cooling Sensor Intra-Sewi KNX TH-Pr • Version: 11.06.2018 • Technical changes and errors excepted.
  • Page 35: General Setpoint Values

    Starting heating/cooling setpoint (in 0.1 °C) -300…800; 210 valid until 1st communication (not upon saving the setpoint value after programming) Sensor Intra-Sewi KNX TH-Pr • Version: 11.06.2018 • Technical changes and errors excepted.
  • Page 36: Standby Setpoint

    Reduce heating setpoint (in 0.1°C) 0…200; 30 (for heating) Increase cooling setpoint (in 0.1°C) 0…200; 30 (for cooling) Eco setpoint Eco mode is usually used for night mode. Sensor Intra-Sewi KNX TH-Pr • Version: 11.06.2018 • Technical changes and errors excepted.
  • Page 37: Setpoint Values For Frost/Heat Protection (Building Protection)

    Level 2 • common control variable are used for Level 1+2 Use control variable for 4/6-way valve No • Yes (only for common control variables in level 1) Sensor Intra-Sewi KNX TH-Pr • Version: 11.06.2018 • Technical changes and errors excepted.
  • Page 38: Temperature Threshold Values

    During initial commissioning, a threshold value must be defined, which will be valid until the first communication with a new threshold value. For units which have already Sensor Intra-Sewi KNX TH-Pr • Version: 11.06.2018 • Technical changes and errors excepted.
  • Page 39: Switching Output

    • on change to 1 and periodically • on change to 0 and periodically Cycle 5 s • 10 s • 30 s… • 2 h (only if sending periodically is selected) Sensor Intra-Sewi KNX TH-Pr • Version: 11.06.2018 • Technical changes and errors excepted.
  • Page 40: Block

    In the 1st level, heating is controlled by a PI control, which allows to either enter control parameters or select predetermined applications. In the 2nd level (therefore only in case of 2-level heating), heating is controlled via a PI or a 2-point-control. Sensor Intra-Sewi KNX TH-Pr • Version: 11.06.2018 • Technical changes and errors excepted.
  • Page 41 PI control with predetermined application: This setting provides fixed parameters for frequent applications. Control type • PI control Setting of the controller by • Controller parameter • specified applications Sensor Intra-Sewi KNX TH-Pr • Version: 11.06.2018 • Technical changes and errors excepted.
  • Page 42 1 bit object (on/off) or an 8 bit object (on with percentage/off). Control variable is a • 1 bit object • 8 bit object Value (in %) 0...100 (for 8 bit object) Sensor Intra-Sewi KNX TH-Pr • Version: 11.06.2018 • Technical changes and errors excepted.
  • Page 43: Cooling Control Level 1/2

    You should set the time appropriate to the cooling system at this point (observe manufacturer's instructions). Maximum control variable is reached 1...5 at setpoint/actual difference of (in °C) Reset time (in min.) 1...255; 30 Sensor Intra-Sewi KNX TH-Pr • Version: 11.06.2018 • Technical changes and errors excepted.
  • Page 44 1 bit object (on/off) or an 8 bit object (on with percentage/off). Control variable is a • 1 bit object • 8 bit object Value (in %) 0...100 (for 8 bit object) Sensor Intra-Sewi KNX TH-Pr • Version: 11.06.2018 • Technical changes and errors excepted.
  • Page 45: Humidity Measurement

    Humidity threshold values Activate the required air humidity threshold values. The menus for setting the th- reshold values are displayed. Use threshold value 1/2/3/4 Yes • No Sensor Intra-Sewi KNX TH-Pr • Version: 11.06.2018 • Technical changes and errors excepted.
  • Page 46: Threshold Value 1, 2, 3, 4

    Object value limit (max.) in 0.1%RH 1…1000 Type of threshold value change Absolute value • Increase/decrease Increment 0.1% RH • ... • 2.0% RH • ... • 20.0% RH (upon increase/decrease change) Sensor Intra-Sewi KNX TH-Pr • Version: 11.06.2018 • Technical changes and errors excepted.
  • Page 47: Switching Output

    Blocking object value before first communi- 0 • 1 cation Behaviour of the switching output On block • Do not send message • send 0 • send 1 Sensor Intra-Sewi KNX TH-Pr • Version: 11.06.2018 • Technical changes and errors excepted.
  • Page 48: Humidity Pi Control

    Use humidity control No • Yes General control Sensor Intra-Sewi KNX TH-Pr can be used to control one- or two-level dehumidifi- cation or combined humidification/dehumidification. Type of control • One-level dehumidification • Two-level dehumidification •...
  • Page 49: Controller Setpoint

    (not upon saving the setpoint value after programming) Object value limit (min.) in % 0…100; 30 Object value limit (max.) in % 0…100; 70 Sensor Intra-Sewi KNX TH-Pr • Version: 11.06.2018 • Technical changes and errors excepted.
  • Page 50: Dehumidification And/Or Humidification

    On release, the control variable follows the rule again. When blocked, the control variable shall • do not transmit anything • send a value Value in % 0...100 (if a value is sent) Sensor Intra-Sewi KNX TH-Pr • Version: 11.06.2018 • Technical changes and errors excepted.
  • Page 51: Dewpoint Measurement

    During initial commissioning, an offset must be defined which is valid until the first communication of a new offset. For units which have already been taken into service, the last communicated offset can be used. Sensor Intra-Sewi KNX TH-Pr • Version: 11.06.2018 • Technical changes and errors excepted.
  • Page 52: 2.Switching Output

    • on change to 0 and periodically Send cycle 5 s • 10 s • 30 s… • 2 h (is only sent if periodically is selected) Sensor Intra-Sewi KNX TH-Pr • Version: 11.06.2018 • Technical changes and errors excepted.
  • Page 53: 3.Blocking

    = 0  send 0 Switching output sends on change to 0 and periodically 5.11. Absolute humidity The absolute air humidity value is detected by the Intra-Sewi KNX TH-Pr and can be output to the bus. Use measured values No • Yes Sending pattern •...
  • Page 54: Comfort Field

    Parameter setting 5.12. Comfort field The Sensor Intra-Sewi KNX TH-Pr can send a message to the bus if the limits of the comfort field are exceeded. In this way, it is for example possible to monitor complian- ce with DIN 1946 (standard values) or even to define your own comfort field.
  • Page 55: Control Variable Comparator 1/2

    Object value prior to first call for: - Logic input 1 0 • 1 - Logic input ... 0 • 1 - Logic input 16 0 • 1 Sensor Intra-Sewi KNX TH-Pr • Version: 11.06.2018 • Technical changes and errors excepted.
  • Page 56: 1.And Logic

    Output value 1 • 0 if logic = 0 Output value 1 • 0 If block is active Output value if 1 • 0 monitoring period is exceeded Sensor Intra-Sewi KNX TH-Pr • Version: 11.06.2018 • Technical changes and errors excepted.
  • Page 57: 1.Block

    • At value 1: block | At value 0: release • At value 0: block | At value 1: release Blocking object value before first call 0 • 1 Sensor Intra-Sewi KNX TH-Pr • Version: 11.06.2018 • Technical changes and errors excepted.
  • Page 58: 2.Monitoring

    Logic input 7 inverted Logic input 8 Logic input 8 inverted Logic input 9 Logic input 9 inverted Logic input 10 Logic input 10 inverted Logic input 11 Sensor Intra-Sewi KNX TH-Pr • Version: 11.06.2018 • Technical changes and errors excepted.
  • Page 59 Switching output 4 Humidity Switching output 4 Humidity inverted Switching output coolant temperature Switching output coolant temperature inverted Ambient climate is comfortable Ambient climate is uncomfortable Comfort temperature controller active Sensor Intra-Sewi KNX TH-Pr • Version: 11.06.2018 • Technical changes and errors excepted.
  • Page 60: Connection Inputs Of The Or Logic

    Switching output AND logic 2 inverted Switching output AND logic 3 Switching output AND logic 3 inverted Switching output AND logic 4 Switching output AND logic 4 inverted Sensor Intra-Sewi KNX TH-Pr • Version: 11.06.2018 • Technical changes and errors excepted.
  • Page 62 Elsner Elektronik GmbH Control and Automation Engineering Sohlengrund 16 75395 Ostelsheim Phone +49 (0) 70 33 / 30 945-0 info@elsner-elektronik.de Germany +49 (0) 70 33 / 30 945-20 www.elsner-elektronik.de Technical support: +49 (0) 70 33 / 30 945-250...