3.
The weather-sealing gasket is affixed to the top side of the IMV mounting flange
and may be stuck to the bottom of the enclosure. Remove any remaining gasket
that is adhered to the bottom of the cabinet.
CAUTION – Equipment damage. The gasket area should be clean and
free of any materials that may hinder the seal of a new gasket. An
improper gasket seal may allow moisture or dirt to enter the enclosure
and damage the electronic components.
3.6
Install the new G5 IMV
CAUTION – Equipment damage. The µFLO
temperature range differs from previous models of the µFLO. The
µFLO
(-40 °C and +70 °C).
To install the replacement G5 IMV, perform the following steps:
1.
Place the clean weather sealing gasket over the upper body of the IMV
assembly and move the gasket down to the mounting plate just below the
electronic board (Figure 2, µFLO IMV replacement (for illustrative purposes
only), on page 8).
2.
Carefully move the IMV up into the access cutout.
3.
Place the split washer, then the flat washer on the screw and screw into the
mounting plate and up into the corresponding screw hole.
4.
Repeat step 3 for the remaining mounting screws.
5.
Securely tighten all eight mounting screws to keep out external environmental
elements.
6.
Reinstall field wiring and cable connections to the new µFLO
board. Use Figure 3 for component and terminal locations and the information in
Table 2 to determine if the connector requires rewiring to a new terminal.
WARNING – Bodily injury and property damage. Wiring peripheral
devices to the flow computer electronic board should be performed
prior to applying power. Do not apply power until instructed to do so.
G5
is rated for ambient temperatures between -40 °F and +158 °F
G5
flow computer operating
G5
main electronic
2105515-001 rev. AB | 9