Installation Work (Option) - FG Europe LMTA Series Installation Manual

Wall mounted type
Table of Contents

Advertisement

External input and output
12.1.
12.1.1. External input
• Indoor unit functions such as Operation/Stop or Forced stop can be done by using
indoor unit terminals.
• "Operation/Stop" mode or "Forced stop" mode can be selected with function setting of
indoor unit.
• A twisted pair cable (22 AWG) should be used. Maximum length of cable is 150 m.
• Use an external input and output cable with appropriate external dimension, depending
on the number of cables to be installed.
• The wire connection should be separate from the power cable line.
● Dry contact terminal
When a power supply is unnecessary at the input device you want to connect, use the Dry
contact terminal.
*1
Connected device
*1: The switch can be used on the following condition: DC 12 V to 24 V, 1 mA to 15 mA.
Operation behavior
● Input signal type
ON
Edge
OFF
● When function setting is "Operation/Stop" mode 1.
Input signal
OFF → ON
Operation
ON → OFF
Stop
● When function setting is "Forced stop" mode.
Input signal
OFF → ON
Forced stop
ON → OFF
Normal
* When the forced stop is triggered, indoor unit stops and Operation/Stop operation by a
remote controller is restricted.
● When function setting is "Operation/Stop" mode 2.
Input signal
OFF → ON
Operation
ON → OFF
Stop (R.C. disabled)
12.1.2. External output
• A twisted pair cable (22AWG) should be used. Maximum length of cable is 25 m.
• Use an external input and output cable with appropriate external dimension, depending
on the number of cables to be installed.
• Output voltage: Hi DC12V±2V, Lo 0V.
• Permissible current: 50mA
Output select
● When interlocking with external device
Connected
device
Relay (Locally purchased)
or
● When displaying "Operation/Stop"
Resistor
LED
Connected device
Operation behavior
*If function setting "60" is set to "00"
Refer to "16 FUNCTION SETTING".
En-8
PCB
1
Connector
2
(CN2)
3
Command
Command
Command
PCB
PCB
Connector
(CN3)
12.1.3. Connection methods
Wire modifi cation
• Remove insulation from wire attached to wire kit connector.
• Remove insulation from locally purchased cable. Use crimp type insulated butt
connector to join fi eld cable and wire kit wire.
• Connect the wire with connecting wire with solder.
IMPORTANT: Be sure to insulate the connection between the wires.
Locally purchased
Solder and insulate the connected parts.
Wired remote controller
12.2.
2-wire type
White
Red
Remote controller
Factory setting
Disconnect the jumper (JM9).
NOTES: Be sure to change the DIP SW to the corresponding remote controller.
When a 2-wire remote controller is connected to a "3WIRE" setting, power will
not be supplied.
When a 3-wire remote controller is connected to a "2WIRE" setting, a
communication error will be detected.

13. INSTALLATION WORK (option)

Front panel, control box cover removal
13.1.
(1) Remove the front panel. (Refer to "9.1. Front panel removal".)
(2) Remove 2 screws, then remove the control box cover.
Connector
(CN3)
External connect kit (option)
DIP switch
Remote
controller
cable
Connecting
"2 WIRE"
the Optional
parts
Screw
Screw
Print circuit board
(PCB)
3-wire type
Black
White
Red
Remote
controller
cable
Remote controller
Set to "3 WIRE"
Control box