Commissioning
Use the Philips Field App to add a switch to an EasySense group. An App User Manual
can be found at www.philips.com/easysense. Follow the ow of either "Create group" or
"Add to group" until the "Adding wireless switch" screen shows up. Simultaneously press
the "On" and "O " buttons for at least 4 seconds to move the switch into commissioning
mode.
Upon entering commissioning mode the LED indicator ashes at a 500msec duty cycle
for 30 seconds (500 msec on/500 msec o ). The luminaire with Easysense will blink
twice when the zigbee channel is matched. Finish the work ow on the App for creating
or adding to the group.
A 30 second time-out is used during commissioning mode. If no reaction is received from
the EasySense for 30 seconds, the device will move back to the decommissioned state.
When the device is commissioned, it can only enter commissioning mode again after
being properly decommissioned.
When the device is commissioned, all commission data is stored in the switch memory.
This memory is held even in the event of a battery changeout.
Scene control and scene setting
Pressing a Scene button on the switch will instruct the sensors and lighting in the group
to go to their programmed setting. Scenes can be custom con gured through the Philips
Field Apps. See the EasySense App User Manual on www.Philips.com/easysense. The
default settings are: Scene 1-- 60% light output; Scene 2 – 20% light output.
Decommissioning the switch
Decommissioning is achieved pressing the decommission
button and holding for at least 1 second. See diagram below
for location of the button, which can be accessed with a
paper clip. After decommissioning, the switch is out of the
network and can be re-added to a group by following the
commissioning procedure.
ON
SCENE 1
SCENE 2
Decommission button
OFF
Button Cover Access Slot
(also location of battery insulator strip on new switch)
Battery LED Indication
Button state
Battery level – Normal ( > 2.5V)
Any button in
RED LED blink
pressed state
6 cycles, 50ms On –
100ms O
All buttons in
RED LED O
released state
Battery replacement and service
To replace the battery, disassemble the switch from the wall to access the Switch
Assembly. Locate the "Button Cover Access Slot" at the bottom of the Button Cover
Assembly (see drawing). Gently pry with a screwdriver to separate the cover. The battery
will be visible pressed against the switch circuit board by the battery clip. Carefully
remove the old battery. Replace only with lithium button cell battery CR2032. Be sure
the battery "+" is facing the battery clip. Snap the cover back onto the Button Cover
Assembly with the battery at the lower end of the switch. Re-assemble the switch
to the wall.
Other than battery replacement, this switch is non-serviceable. A damaged or
non-functioning switch should be completely replaced and should not be repaired.
This product contains a lithium button/coin cell battery. If a new or used lithium
button/coin cell battery is swallowed or enters the body, it can cause severe internal
burns and can lead to death in as little as 2 hours. Always completely secure the battery
compartment. If the battery compartment does not close securely, stop using the
product, remove the batteries, and keep it away from children. If you think batteries
might have been swallowed or placed inside any part of the body, seek immediate
medical attention.
The cells shall be disposed of properly, including keeping them away from children; and
Even used cells may cause injury.
Battery level – Low
Battery level – Dead
( 2.3 < Low < 2.5V)
( < 2.3V)
RED LED ash once
RED LED O
50ms On
RED LED O
RED LED O