1. DESCRIPTION

The TCP-485 Serial/Ethernet converter allows you to connect Full Gauge controllers with the Sitrad
supervisor software over an Ethernet data network using the communication standard TCP/IP. Nowadays
many companies have Ethernet cabling already installed in their premises. With the TCP-485 converter you
can use your Company installed cabling instead of installing new cabling for the RS-485 network of
controllers. The system is composed of an Ethernet/RS-485 converter connected to the Ethernet network (it
can be Internet, Intranet or a direct connection to the computer) and the Sitrad that connects directly to the
Ethernet/RS-485 converter using TCP/IP. The converter then communicates with the controllers connected
to it and translates the RS-485 electric standard used by the controllers to the TCP/IP communication
protocol used in computer network interconnections.

2. APPLICATION

- Installations that already have an Ethernet network and do not have conditions to run new cabling network.
- Centralize data acquisition from many remote locations in one server without the need to have a dedicated
computer for each remote location.
NOTE: The TCP-485 converter is designed to work only with Full Gauge Controls devices.

3. TECHNICAL SPECIFICATIONS

- Converter Power Supply: 12 Vdc.
- Power supply unit supplied with the converter: Input: 100-240Vac (50/60Hz)
- Operating temperature: 0 a 50°C
- Operating humidity: 10 a 90%UR
- Amount of devices supported by the converter: 32
- Indicator LEDs:
RUN: indicates the converter is ON
TX: indicates transmission status
RX: indicates transmission status
CON: indicates that the application SITRAD is connected to the converter
- Ethernet Speed: 10Mbps
- Connections:
-RJ-45 connection for connecting with PC using twisted pair cable supplied together with the converter.
- One port Isolated RS-485 for connection to instrument 32, without the need for termination.
- Direct ethernet cable-80cm (without crossover) supplied with the converter.
IMPORTANT NOTICE:
If the "LAN" LED indicator in the RJ-45 connector does not light up upon connecting the TCP-485
converter directly to the network adapter of the computer, you may need to use a crossover cable
(not supplied by Full Gauge) or to connect the computer and the converter via a HUB or Switch.
4. INSTALLATION AND OPERATION (DHCP MODE - DEFAULT
CONFIGURATION)
Connect interface terminals A and B with the respective A and B terminals on the
instruments;
With the TCP-485 powered on, use an Ethernet cable to connect it to a router (router/switch) in the RJ-45
connectors according to the picture below:
RS-485
A
B
A B
B
A
MT-530
super
Instrument
TCP-485
RJ45
SITRAD 4.12
Download a compatible version from: http://www.sitrad.com
Step 1: With the TCP configured, open Sitrad, click on "Configuration" and then on "Options".
Step 2:
In the window that opens, select the option "Use Ethernet communication". Then click on the "Configure
Ethernet" button below.
TCP-485
CONVERTER
SERIAL / ETHERNET
Ver.03
Output: 12Vdc / 2A
connecting blocks
A
B
Router
Step 3: In the window that opens, click on the button "New Converter".
Step 4: In the window that opens, choose the desired option. As an example we will use the option "Search
the network".
Step 5: Once it has been located, select TCP-485 and then click on the button "Register converter", select
version 3 and click "OK".
If the user has the TCP-485 configured with a fixed IP, follow the steps below to connect it to a computer:

5. NETWORK CONFIGURATION IN STATIC IP MODE

For direct connection with a PC, the IP mode must be changed to static. See the step by step procedure :
Step 1:
Using a computer connected to the same network as the TCP-485 (cable or wireless), download
and
EthernetConfig (Windows version only) from the site:
http://www.sitrad.com/atualizacaoresp.asp
Step 2:
Run EthernetConfig and click on the icon "Broadcast Search". The TCP-485 connected to the network will
be shown after the search is done. See image below:
Step 3:
Click on the "Configuration" menu and click on the box "Network configuration" on the following screen,
change the IP Mode to static, and then click on "save changes".

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the TCP-485 and is the answer not in the manual?

Questions and answers

Summary of Contents for Full Gauge TCP-485

  • Page 1 - Direct ethernet cable-80cm (without crossover) supplied with the converter. version 3 and click "OK". If the user has the TCP-485 configured with a fixed IP, follow the steps below to connect it to a computer: IMPORTANT NOTICE: If the "LAN" LED indicator in the RJ-45 connector does not light up upon connecting the TCP-485 converter directly to the network adapter of the computer, you may need to use a crossover cable (not supplied by Full Gauge) or to connect the computer and the converter via a HUB or Switch.
  • Page 2 - Connect the converter network cable directly in the computer network card.If the computer is fitted with an old network card, you may need to use a crossover cable, which is not provided by Full Gauge. Upon doing Reset key this your computer will lose access to the network and the Internet.

Table of Contents