gesis® P MS8-360-1L
83.020.0110.1
gesis® P MS8-360-1Lb
83.020.0110.2
gesis® P MS8-360-1LSL
83.020.0110.3
gesis® P MS8-360-SLb
83.020.0111.1
gesis® P MS8-360-SLSL
83.020.0111.2
gesis® presence detector switching
DANGER
Only trained electricians may install and commission this device. They
must have read and understood this instruction manual before the
installation.
Do not open the device. Do not insert any foreign objects. Keep the device
away from water and fire.
Only connect or disconnect the device if it hast been de-energised.
The relevant standards, directives, regulations and provisions of the parti-
cular country are to be observed.
CAUTION
Since
the
presence
detectors
are
in installation, the appropriate provisions for cable tension relief apply.
If the presence detector is opened, this can't be guaranteed and Wieland makes
no guarantees.
General Description
The gesis® P MS8-360-1L (1Lb, 1LSL, SLb, SLSL) are for light control.They switch
the lighting dependant on movement or brightness, fully automatically or after
activating the control via remote. Brightness threshold and sensitivity of the sensor
can be adjusted individually. The lighting is switched off automatically or after the
last movement and end of the delay time, or is switched off directly via remote.
For covering areas that go beyond the detection range of one detector, slaves
(P gesis® MS8-260 SL ...) are used. The slaves report detection of movement
to the master. The Master controls all further functions. For this reason only the
sensitivity can be set in the slaves.
Please note that all parameters are set with remote gesis® PIR IPD-16A.
The following versions are available:
Master
Master with direct light connection (MAa)
Master for connection of a cross connector
(MAb)
Accessories for cross connector
Master for connecting a slave (MASL)
Slave
Slave with direct light connection (SLa)
Slave with connection for another slave (SLSL) gesis® P MS8-30-SLSL 83.020.0111.2
Function
Input*
male Plug
Type
GST18
MAa
Master
3-pole, bw.
MAb
Master
3-pole, brown
230 V AC
MASL
Master
3-pole, bw.
SLa
Slave
from master
5-pole black
or slave
SLSL
Slave
SV
H
Application
The sensors are for use in offices, schools, meeting rooms and similar locations.
The gesis® P MS8-360-1L... are suitable for small and large rooms, because they
can be combined with several slaves gesis® P MS-360-SL.
GST18i3
L PE N
MAa
GST18i3
L` PE N
L PE N
L N L`
SV
Doc. # BA000957 – 06/2015 (Rev. A)
gesis
Hotline:
Tel.: +49 (951) 9324-996
Fax: +49 (951) 9326-996
Email: BIT.TS@wieland-electric.com
Internet: www.gesis.com
integrated
directly
into
the
Type
Part No.
gesis® P MS8-360-1L
83.020.0110.1
gesis® P MS8-360-1Lb 83.020.0110.2
92.030.0153.1
gesis® P MS8-360-
83.020.0110.3
1LSL
Type
Part No.
gesis® P MS8-360-SLb 83.020.0111.1
Output*
female Plug
Type
GST18
3-pole, white
230 V AC
to slave
5-pole, white
230 V AC
3-pole, white
to slave
5-pole, white
Cross connector
Lighting
*cable length 0.5 m
GST18i3
L` PE N
L PE N
H
GST18i3
L PE N
MAb
H
gesis
P MS8-360-1L | MS8-360-1Lb | MS8-360-1LSL | MS8-360-SLb | MS8-360-SLSL
®
Wieland Electric GmbH
Brennerstraße 10-14
96052 Bamberg
Tel. +49 (951) 9324-0
Fax +49 (951) 9324-198
Internet: www.wieland-electric.com
Email: info@wieland-electric.com
Operating Mode
The gesis® P MS8-360-1L... can control the lighting in two ways:
In the first mode, the lighting is switched on with the remote control
gesis® PIR IR B-04 IPD and switches off automatically when leaving the room after
a specified delay time.
In the second mode the lighting is switched on and off automatically. If there is
sufficient daylight (above set value), the lighting is not switched on.
Default settings
Various functions of the presence detectors can be changed.
Master gesis® P MS8-360-1L:
plug-
automatic ON/OFF
delay time 15 minutes
brightness threshold 200 Lux
sensitivity on second-highest level
Installation
Both presence detectors are pre-assembled with plug connectors. The electrical
connections are only plugable. For the necessary plug-family please refer to the
table above.
All presence detectors are for ceiling installation and are fixed through a hole with a
diameter of 86 mm. The maximum thickness of the material is 30 mm.
Technical specifications
Type
Network voltage / Fre-
quency
Standby Consumption
Relay
Load
Ohmic load
Fluorescent tubes
(not compensated)
Halogen incandescent
bulbs
Max. capacity
Max. starting current
Operating range
LUX range
Delay time
Sensitivity
Ambient temperature
Protection class
Humidity
Color (housing)
Mounting hole diameter
Montage max.
Materialdicke
Accessories remote control
... for programming
... for users
GST18i3
GST18i5
L L` PE N Info
MASL
GST18i5
L L` PE N Info
MASL
SLSL
Updated:
06/2015
© 2015 Wieland Electric GmbH
Slave gesis® P MS8-SL:
sensitivity on second-highest level
gesis® P MS8-360-1L...
gesis® P MS8-360-SL...
230 V / 50 Hz
230 V / 50 Hz
<1 W
<1 W
NO 230 V, 10 A,
µ-contact
2300 W
1200 VA
2300W
140 µF
165 A / 20 ms
Ø 8 – 12 m, 360°
Ø 8 − 12 m, 360°
50 – 1000 Lux
15 – 180 min
four level
four level
0 to +50°C
0 to +50°C
IP20
IP20
20 – 95% without
20 – 95% without
condensation
condensation
white
white
Ø 86 mm
Ø 86 mm
30 mm
30 mm
gesis® PIR IR B-21 IPD
gesis® PIR IR B-21 IPD
(83.020.0122.0)
(83.020.0122.0)
gesis® PIR IR B-04 URM
(83.020.0122.1)
GST18i3
L` PE N
SLa
H
GST18i5
GST18i3
L L` PE N Info
L` PE N
SLa
H
EN page 3

Advertisement

loading

This manual is also suitable for:

Gesis p ms8-360-slbGesis p ms8-360-1lslGesis p ms8-360-1lbGesis p ms8-360-slsl