Hide thumbs Also See for TPD-800A:

Advertisement

Quick Links

iPOWER TPD-800A User Manual
iPOWER TPD-800A
User Manual
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the TPD-800A and is the answer not in the manual?

Questions and answers

Summary of Contents for iPower TPD-800A

  • Page 1 TPD-800A User Manual iPOWER TPD-800A User Manual...
  • Page 2: Table Of Contents

    5. Individual Current, Total Current, Temperature & Humidity Over Limit Monitoring…………………..5 6. Self-checking Parameter Monitoring ......................5 7. Stopping Alarm Monitoring ........................5 8. Master / Slave TPD-800A Configuration ....................6 9. Daisy-chain Connection Method ......................6 10. Radialized Connection Method ......................6 11.
  • Page 3: Ⅰ. Tpd-800A Introduction

    TPD-800A User Manual Ⅰ. TPD-800A Introduction TPD-800A can monitor, control and manage the power supply of many equipments in cabinets in data room all over the world through LAN or WAN. For meeting with the restrictions and requirements in different environment, TPD-800A supplies many connection methods;...
  • Page 4: Ⅲ. Applied Range

    Ⅲ. Applied Range 1. TPD-800A can be applied to server cabinet, network cabinet etc. 2. The socket quantity (8 or 12) and socket standard (C13, C19, NEMA5-15R, NEMA5-20R) of TPD-800A can be selected. 3. TPD-800A conforms to RoHS instruction, suitable for 110VAC and 220VAC power supply, can meet the customers’...
  • Page 5: Ⅴ. Mounting Method

    Horizontal installation. Ⅵ. H ardware I ntroduction 1. Power on & Self-check The buzzer makes a sound when TPD-800A is connected with AC power source, LED screen lightening and sequentially display 8.8.8. 8.8.8. (it means digitron is normal, any different display means fault), software version number (for example U0.0...
  • Page 6: Self-Checking Parameter Monitoring

    9.2 Set one TPD-800A as master and the others as slaves. One master can daisy-chain 9pcs TPD-800A slave at most. 9.3 One end of the network wire connects to the LINK port of the master TPD-800A, the other end connects to...
  • Page 7: Radialized Connection Method

    TPD-800A User Manual the SER port of the first slave TPD-800A, then use one end of another wire connects to the LINK port of the first slave TPD-800A, the other end connects to the SER port of the next slave TPD-800A. Use the same way to connect other slave TPD-800A.
  • Page 8 11.11 Power off the TPD-800A 11.12 Power on the TPD-800A, LED screen will show the new version which means the software upgrade successful and then it can work normally.
  • Page 9: Ⅶ. Software Introduction

    TPD-800A User Manual Ⅶ. Software Introduction 1. Software overview This software is a technology that employs the total embedded system solution. It is based on the monitoring technology of SNMP standard protocols, encryption of SSH data transmission, sensor network node technology and other high-tech technologies.
  • Page 10 Configure the device series number, input outlet name as well as the interval of sequential power on/off, details as below: a) " TPD-800A Address No": each device has a unique series number; the user can not normally monitor and manage the device if the displayed figure is not the same as the device series number.
  • Page 11 TPD-800A User Manual a) IP address: LAN or WAN IP address, the default IP is 192.168.1.163 b) Sub-net Mask: correspond with IP; the default sub-net mask is 255.255.255.0 c) Gateway: correspond with IP; the default gateway is 192.168.1.1; d) DNS address: the default DNS is 0.0.0.0, any DNS address of normal domain name resolution, make sure the e-mail can be send successfully Note: network configuration information will be valid after system reboot.
  • Page 12 TPD-800A User Manual b) E-mail alarm: ♦Select “Enable e-mail alarm" ♦POP3 address: receive e-mail server address, e.g. Sina POP3 address: pop.sina.com; ♦SMTP address: deliver e-mail server address, e.g.Sina SMTP address: smtp.sina.com; ♦Port: delivery e-mail port (general e-mail port: 25), input the corresponding output port according to e-mail level.
  • Page 13 TPD-800A User Manual ♦ Set and save the HTTP port according to the network environment, the default HTTP port is 80; ♦ Select "Enable" to start and save HTTP, set the HTTP enable and can not be closed Note: the setting will be valid after system reboot.
  • Page 14 TPD-800A User Manual c) Click "Update" d) Return to prompt information automatically when file submitting successfully (letters in blue), which means the update document submitted successfully. e) Waiting for the system pop the login window after software system initialized when file submit successfully.
  • Page 15 TPD-800A User Manual leading-in MIB file on the SNMP management platform, user can monitor and manage the device status information and alarm Trap information after translating and editing success, the details information of device status are as detailed in figure 2-1, figure 2-2, 1).
  • Page 16 TPD-800A User Manual 2) According to the setting of the SNMP on the IE browser interface, TRAP information will be sent to Trap Destination automatically, the time information of alarm, device name and the alarm type will be included in the TRAP information.
  • Page 17 View the sensor status, e.g the current status of the temperature/humidity/door /water/smoke sensors and the threshold of temperature/humidity. For instance: STATUS ABCDEF 5: View the status of output 5 of the TPD-800A whose series number is ABCEDF, e.g the statue of switch on/off, load current and threshold of current.
  • Page 18 Restart all the output of devices This option only require output number, restart only one outlet at a time For instance: REBOOT ABCDEF 1: restart the output 1 of TPD-800A whose series number is ABCDEF 5) SHOW "SHOW" command line can be used to read the network configuration information, system information, user...
  • Page 19 TPD-800A User Manual View the e-mail alarm setting, e.g POP3 server address, SMTP server MAIL address, e-mail sending port, e-mail sender's address and password, receive address, carbon copy address, interval of alarm ONINTERVAL View the power on interval of this 【ADDRESS】...
  • Page 20 TPD-800A User Manual Note: HTTP configuration will be valid after reboot C. TELNET Command line input format: Set TELNET 【OPTION】 【OPTION】 as detailed in figure 3-6-c Figure 3-6-c the description table of TELNET OPTION 【OPTION】 Description ENABLE Set the HTTP enable...
  • Page 21 TPD-800A User Manual SETC Set the character string of community TRAPC TTAP character string of community REPTIME The interval of Trap sending DES1 The destination 1 of Trap information to be sent DES2 The destination 2 of Trap information to be sent...
  • Page 22 TOTALC Set the highest value of the total load current of phase C For instance: SET THRESHOLD ABCDEF TEM1 L=0 Set the lowest value of temperature sensor 1 of TPD-800A whose series number is ABCDEF to be 0 Note: Temperature rating: -40℃~215 ℃;...
  • Page 23 TPD-800A User Manual Humidity rating: 0%~100%; Current rating: 0~-10A H. TIMING "SEG TIMING" adjust the device time, set the time of device power on/off Command line input format: SEG TIMING 【ADDRESS】 【OPTION】 【ADDRESS】: the series number of connected device 【OPTION】...
  • Page 24 TPD-800A User Manual Command line input format: SET ONINTERVAL 【ADDRESS】 【OPTION】 For instance: SET ONINTERVAABCDEF TIME=1 Set the interval of device whose series number is ABCDEF to be 1 second. J) DEVICE "SET DEVICE" to change the device name, output name and serial number.
  • Page 25: Device Daisy-Chain

    A. Log on to IE(Internet Explorer) browser access interface, open the "Device Configuration" and input the device series number in the frame of TPD-800A Address No., check the setting success or not through reading the device status of "Device Control" interface B.
  • Page 26: Frequently Asked Questions

    TPD-800A User Manual Note: A. The daisy-chain device hold the unique hardware series number B. The name can not be repeat when name the new added device. IV. Restore the network configuration Restore the network configuration of hardware, restore IP address, sub-net mask, default gateway, DNS setting, SSH,...

Table of Contents