TTK FG-ALS Installation Instructions

Alarm locating unit

Advertisement

Quick Links

FG-ALS Alarm Locating Unit Installation
1.
Fixing the FG-ALS Alarm Location Unit
The FG-ALS Alarm Location Unit is available in wall mounted version (165 x 85
x 55 mm).
Two of the three cable glands are placed on the FG-ALS Alarm Unit, the last
one can be screwed in the place of plug PG7.
Use the two fixing holes in the lower part of the unit box. Release the higher
part of the box of the lower part which is maintained by two screws. These two
parts could be easily dismounted after mural fixing. Withdraw carefully the
higher part with the PCB (printed circuit board).
2.
Connection and Adjustment

2.1 Power Connection

2.2 Connection of the
Dry Relays
2.3.Serial Interface
Physical Support
2.4. Serial Link Parameters
2.5. Supported Protocol
2.3. Adjustment of the
Detection Sensitivity
FG-ALS Alarm Locating Unit Description
The FG-ALS Alarm Location Unit is designed to be used with two kinds of TTK analogue sense cables: random FG-ECS, FG-ACS
and pre-connected sense cables FG-ECX, FG-ACX. It allows the leak detection and location of liquids.
The appearance of a fault (leak, cable break) is detected in the following way:
An audible alarm is triggered;
A luminous diode turns on;
A dry contact is activated to transfer the alarm information to remote monitoring equipments.
JBUS/MODBUS protocol is communicated to BMS.
The display on the front face shows the leak location (in metre).
To stop the audible alarm, press the "reset" button. The diode and the dry contact remain activated as long as the fault is pre-
sent. When the fault disappears, the diode switched off, the relay returns to its original normal status and the content of the
display disappears.
The maintenance of the system is recommended for every six months minimum.
FG-ALS Alarm Locating Unit Installation Instructions v1.5-092014
FG-ALS
Alarm Locating Unit
Installation Instructions
FG-ALS Alarm Unit is powered into 230-240 VAC only.
The maximum section of the cable is of 14 AWG for 230-240 VAC. Use PG9 cable gland for the
cable 230 V.
The dry relays are free of potential. The maximum section of the cables is of 18 AWG.
Dry Contact for Leak:
The leak contact transfers the information of leak to a PC (or supervisor), allowing automated
equipment control.
Dry Contact for Cable Break:
A specific contact is activated in case of cable break. A power supply failure also activates this
contact.
Relay of Leak and Relay of Cable Break:
Simple relay: COM-NO-NC
Max. commutated Voltage: 125 VAC / 60 VDC
Opto-isolated, Two-Wire RS485
9500 Baud, 8 Data Bits, 1 bit Stop, no Parity
Modbus, Functions 3 and 4
You can adjust the detection sensitivity, using the potentiometer (P1). The adjustment factory
corresponds to the maximum sensitivity (1 turn).
The FG-ALS Alarm Location Unit
wall mounted version contains:
1 FG-ALS Alarm Unit: 230VAC/50Hz
3 PG cable glands: 2 PG7 + 1 PG9
1 Installation Instructions
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the FG-ALS and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for TTK FG-ALS

  • Page 1 FG-ALS Alarm Locating Unit Description The FG-ALS Alarm Location Unit is designed to be used with two kinds of TTK analogue sense cables: random FG-ECS, FG-ACS and pre-connected sense cables FG-ECX, FG-ACX. It allows the leak detection and location of liquids.
  • Page 2 To connect the FG-CLC leader cable, refer “FG-SYS installation guide” chapiter 1, sector 3.3 “Connection of FG-CLC leader ca- ble”. The FG-CLC leader cable, connected to the FG-ALS alarm unit with a female connector, at its extremity. The beginning of the sense cable thus corresponds at its extremity with a male connector.
  • Page 3 This brochure with its photos, illustrations and charts were carefully prepared, but may only be taken as examples. TTK cannot guarantee that the information given contains no errors or omissions and will accept no responsibility related to the usage of its equipment. TTK's only obligations are those set forth in the Standard Terms and Conditions of Sale and will not under any circumstances be held liable for any incidental, indirect or consequential damages arising from the sale, resale or misuse of this product.

Table of Contents