Model BTC-1
Backup Tone Card
INTRODUCTION
The Model BTC-1 Backup Tone Card from
Siemens Industry, Inc. provides two tones
for the MXLV System that can be selected
by dipswitches. This card can be installed on
top of the ACM-1 to provide backup of the
two primary tones should the tone generator
of the ACM-1 fail. The BTC-1 can also be
installed on the OCC-1 Output Control Card
module to provide a default tone when the
low power riser fails and when the OCC-1
loses contact with the MMB.
Select the two backup tones on switch S1 by
matching SW1-SW4 and SW5-SW8 to the
CSG-M (AccuLINK) configuration tone selec-
tions. Table 1 on the next page shows the
switch settings for each available tone.
For additional information on the Voice
System, refer to the MXLV Manual, P/N
315-092036.
INSTALLATION
Remove all system power before installa-
tion, first battery and then AC. (To power
up, first connect the AC and then the battery.)
1. Remove the card from its protective bag.
Siemens Industry, Inc.
Building Technologies Division
Florham Park, NJ
P/N 315-090919-8
2. Refer to the function section of the CSG-M
configuration printout for the tones to be
configured.
3. Set the desired tones on switch S1 using
dipswitches SW1-SW4 for the first tone
selection and dipswitches SW5-SW8 for
the second tone selection.
a. Refer to Figure 2 or 3 on page 3
for the location of S1.
b. Refer to Table 1 for the switch set-
tings and their associated tones.
c. Set the tones (See Note at the top
of the next page).
Do not install the BTC-1 on the ACM-1
or OCC-1 until the system is ready for
the installation of PC cards. Until then,
keep the BTC-1 in its protective bag.
Mounting
The BTC-1 mounts on either the ACM-1
(See Figure 2) or the OCC-1 (See Figure 3)
with two snap-in type standoffs and a comb-
like connector.
1. Install the standoffs and comb connector
in the component side of the ACM-1 or
the OCC-1, whichever is appropriate.
(See Note at top of the next page.)
Siemens Building Technologies, Ltd.
Fire Safety & Security Products
2 Kenview Boulevard
Brampton, Ontario
L6T 5E4 Canada

Advertisement

loading

Summary of Contents for Siemens BTC-1

  • Page 1 SW1-SW4 for the first tone two primary tones should the tone generator selection and dipswitches SW5-SW8 for of the ACM-1 fail. The BTC-1 can also be the second tone selection. installed on the OCC-1 Output Control Card module to provide a default tone when the a.