Edwards 3-REMICA Manual

Edwards 3-REMICA Manual

Remote microphone

Advertisement

Product description

FRONT
The 3-REMICA provides remote paging capability at stations
located throughout a building or campus. The 3-REMICA can
be connected to other remote microphone units to provide up
to 63 stations on the paging circuit.
The 3-REMICA occupies 2 slot positions in a 2-space, 6-space
or 10-space remote annunciator cabinet. When installed in a
cabinet with an annunciator controller, the 3-REMICA must
occupy the slot positions next to the controller.
The 3-REMICA housing assembly provides standoffs for
mounting a Signature single input module when the system
application requires electrical supervision. The 3-REMICA
trouble relay contacts change state whenever an electrical
short or open is detected on either the microphone or audio
inputs, or whenever power is interrupted to the unit.

Specifications

Power requirements
Voltage: 21 to 27 VDC
Current: 52 mA
Space requirements: 2 spaces in annunciator enclosure
Audio Output: 1 VRMS @ 400 Hz to 4 kHz
Trouble relay contacts
Current: 1 A @ 30 VDC resistive
UL rating: Common
Wiring
Termination: All wiring connects to terminal block
Size: 14 AWG (1.5 sq. mm) max.
Resistance: 210 Ω max.
Capacitance: 1 µF
Operating environment
Temperature: 32 to 120°F (0 to 49°C)
Humidity: 93% noncondensing
Installation Sheet
3-REMICA - Remote Microphone
SIDE
05SEP07

Jumper settings

Jumper JP1 and JP2:
Position A: Selects AC supervision when connecting the audio
output to 3-ASU.
Position B: Selects DC supervision when connecting the audio
output to 3-REMICA.

Installation instructions

Warnings
This product contains components that are sensitive to
static electricity. Failure to follow proper handling
procedures to prevent damage from electrostatic
discharge may result in equipment failure.
Ensure the 24VDC riser is deenergized before making
cable connections.
To install the 3-REMICA:
1.
Remove the top module retainer bracket on the inner door
of the remote annunciator enclosure.
2.
Loosen the bottom module retainer bracket.
3.
Insert the bottom of the 3-REMICA into the bottom module
retainer bracket next to the annunciator panel controller.
4.
Tilt the 3-REMICA forward until the top touches the inner
door.
5.
Tighten the bottom module retainer bracket.
6.
Secure the top module retainer bracket to the inner door.
7.
Connect the cable assembly from P3 on the annunciator
panel controller to P4 on the 3-REMICA.
3-REMICA
Remote Microphone
P/N: 387466 REV: 3.0
1 / 2

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 3-REMICA and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Edwards 3-REMICA

  • Page 1 The 3-REMICA provides remote paging capability at stations located throughout a building or campus. The 3-REMICA can Insert the bottom of the 3-REMICA into the bottom module be connected to other remote microphone units to provide up retainer bracket next to the annunciator panel controller.
  • Page 2 Power-limited and supervised. Ω Terminate the KEY IN input with a 1.8 k EOL resistor when it is not used. Wiring must be enclosed in conduit. Figure 1: Field wiring for the 3-REMICA 3-REMICA TB1-19 TB1-20 Signature Single Input Module...

Table of Contents