5.6. Connection of tube for oil sampling for VUC
Preparation for oil sampling is done at the transformer
workshop as part of the tap-changer installation.
– The oil valve (see Fig. 45) should be removed and re-
connected at the end of the draining tube at operable
ground level.
Fig. 45. Oil valve.
Fig. 47. Extra oil sampling valve. The valve is removed and then refitted at the end of the sampling tube.
Extra oil valve shall be removed
and used as a sample valve
Tube ½"
Oil valve
– The tube, through which oil samples are taken, must be
connected to a sample pipe, see Fig. 47. The tube shall be
of ½ inch.
– Information regarding the flanges, view A-A and view B-B,
see Fig. 46.
A - A
O-ring
Ø 44.2 x 5.7
Ø 75
4 x M10
Ø 106
Fig. 46. Sample pipe dimensions.
UCL top cover
1ZSC000562-AAZ en | Installation and commissioning guide UCL/VUCL 41
B - B
Ø 75
45°
Ø 106
Transformer cover
45°
4 x Ø 11