Carrier 53DS-900-062 Installation Instructions
Carrier 53DS-900-062 Installation Instructions

Carrier 53DS-900-062 Installation Instructions

Duct free systems 009-024 cooling only and heat pump high wall units accessory condensate pump

Advertisement

009-024 Cooling Only and Heat Pump High Wall Units

GENERAL

NOTE: Read and become familiar with these instructions
before beginning installation.
The two-part accessory kit (condensate pump and detec-
tion unit) is for use with the size 009 (115v), 012 (230 v),
018 (230v), 024 (230v), high wall fan coil units. Refer to
Table 1 for a list of parts included in this kit.
The condensate pump is designed to provide an 8.2 ft maxi-
mum lift of condensate in situations where space and con-
struction prevent gravity drainage.
A float switch in the detection unit will prevent overflow
while in use and can also act as a safety device when the
user optional alarm contact is utilized. The detection unit comes
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4
PC 111
Tab
3e 2f
Installation Instructions
Part Number: 53DS-900---062 (115 v)
Part Number: 53DS-900---064 (230 v)
Fig. 1 — Accessory Condensate Pump Connections
Catalog No. 534-009
Printed in U.S.A.
Duct Free Systems
Accessory Condensate Pump
Cancels: New
with normally closed (NC) or normally open (NO) alarm con-
tacts (user optional, but recommended).
The normally closed (NC) alarm contact is a dry contact
rated for 8 amps at 250 volts. In the event of a problem such
as a clogged filter or pump discharge line, the alarm contact
can be wired to shut down the entire system and/or initiate
an audible or visual alarm. See Fig. 1.
The pump will operate whenever the condensate level in
the detection unit is high enough to cause the magnetic float
switch to send a signal to start the pump.
Failure to follow instructions properly may result in unit
failure and damage.
Form 40QN-3SI
Pg 1
IIK 619E-09-2
5/1/99
5-99
Replaces: New

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 53DS-900-062 and is the answer not in the manual?

Questions and answers

Summary of Contents for Carrier 53DS-900-062

  • Page 1: Installation Instructions

    Duct Free Systems 009-024 Cooling Only and Heat Pump High Wall Units Accessory Condensate Pump Cancels: New IIK 619E-09-2 5/1/99 Installation Instructions Part Number: 53DS-900---062 (115 v) Part Number: 53DS-900---064 (230 v) with normally closed (NC) or normally open (NO) alarm con- GENERAL tacts (user optional, but recommended).
  • Page 2 SAFETY CONSIDERATIONS INSTALLATION Installation and servicing of air-conditioning equipment NOTE: For ease of installation, it is recommended that the can be hazardous due to system pressures and electrical com- detection unit assembly be installed prior to installation of ponents. Only trained and qualified service personnel should the fan coil unit.
  • Page 3 4. Attach the remaining transparent tubing to the discharge CLEANING AND MAINTENANCE side of the pump assembly (see Fig 1 and 3) and cut dis- charge line accordingly. Maximum vertical height of dis- charge is 20 feet. Be sure condensate is discharged to safe location where the presence of water does not pose any Disconnect all power to unit to avoid possible electrical safety or health hazards.
  • Page 4 Copyright 1999 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 1 4 PC 111 Catalog No. 534-009 Printed in U.S.A. Form 40QN-3SI Pg 4 5-99...

This manual is also suitable for:

53ds-900-064

Table of Contents