Status word (Vendor profile)
Information about the status of the device and messages is indicated in the Status word.
The Status word is composed of 16 bits that have the following meanings:
Bit
Description
Value = 0
0
Not Ready (initial)
1
Not Ready
2
DISABLE
3
NO FAULT
4
STOP 2
5
STOP 3
6
START ENABLE
7
No Warning
8
Reference
Actual value
9
Fieldbus control OFF
10
Not used
11
Not used
12
FC stopped
13
FC not ready
14
Not used
15
Not used
Table 4.
*Comes straight from the frequency converter
**Bits of the State Machine
24-hour support +358 (0)40 837 1150 • Email: fieldbus@vacon.com
Value = 1
READY 1 **
READY 2 **
ENABLE **
FAULT ACTIVE *
NO STOP 2 **
NO STOP 3 **
START DISABLE **
Warning *
Reference = Actual value *
Fieldbus control ON *
Not used
Not used
Running *
FC ready *
Not used
Not used