Page 1
PLEASE READ THESE INSTRUCTIONS PRIOR TO INSTALLATION, INITIAL FIRING, AND BEFORE PERFORMING ANY SERVICE OR MAINTENANCE. THESE INSTRUCTIONS MUST BE LEFT WITH THE USER AND SHOULD BE RETAINED FOR FUTURE REFERENCE BY QUALIFIED SERVICE PERSONNEL. THERMO PRODUCTS, LLC. PO BOX 217 NORTH JUDSON, IN 46366...
The predetermined limit locations on all of the Thermo Pride oil fired furnaces have been tested and approved by Thermo Products, LLC. Any attempt to relocate these safety controls or replace these safety controls with a control that is not approved, or is incompatible, may result in personal injury, substantial property damage or death.
SECTION I. SAFETY SECTION II. GENERAL INSTRUCTIONS A. VENTING B. DRAFT REGULATORS C. DUCT WORK/AIR CONDITIONING D. FILTERS MOUNTED EXTERNAL TO FURNACE E. LIMIT POSITION AND LOCATION F. BURNER INSTALLATION G. BURNER SPECIFICATIONS AND APPLICATIONS H. HEAT EXCHANGER CLEANING INSTRUCTIONS III.
The OH5-85DXE*** furnaces may be installed on combustible flooring. NOTE: The OH5-85DXE*** furnace is approved for closet installation. If the OH5-85DXE*** is installed in a closet, it requires two openings in the closet door for combustion air, each having a minimum area of 162 sq. inches.
Cut hole and extend flue through side casing. A trim collar may be ordered from Thermo Products to hide the gap around the flue pipe. This trim collar, however, is not required for operation. Trim collar/gasket part numbers(s) 14121 / 330073.
All installations and services must be performed by qualified service personnel. C. DUCT WORK/AIR CONDITIONING: If the furnace is used in connection with summer air conditioning (cooling), the furnace should be installed parallel with or on the upstream side of the evaporator coil to avoid condensation in the furnace heat exchanger. If the cooling unit is installed with a parallel flow arrangement, dampers or other means used to control flow of air should be provided to prevent chilled air from entering the furnace.
Page 7
(See Fig. 5). Fig. 5: A typical filter rack and dimensions for the OH5-85DXE*** furnace. PLEASE NOTE: While scribing the return air opening, the filter rack can be held in position by tape or similar temporary means.
The predetermined limit locations on all of the Thermo Pride oil fired furnaces have been tested and approved by Thermo Products, LLC. Any attempt to relocate these safety controls or replace these safety controls with a control that is not approved, or is incompatible, may result in personal injury, substantial property damage or death.
Page 9
All installations and services must be performed by qualified service personnel. Fig. 9: (Top view) Burner insertion illustration When mounting the burner, the upper mounting plate (Fig. 8) must be removed to provide access to the area in front of the combustion chamber. The combustion chamber can then be moved forward or backward slightly to allow for adjustment in positioning the burner tube.
For more specific burner information, specifications or service information, reference the training manual enclosed with each Riello burner or contact: OH5-85DXE*** HIGH FIRE LOW FIRE * Based on #2 domestic heating fuel oil having heating value of 140,000 BTU per gallon.
All installations and services must be performed by qualified service personnel. H. HEAT EXCHANGER CLEANING INSTRUCTIONS: cWARNING: THE HEAT EXCHANGER MUST BE CLEANED BY A QUALIFIED SERVICE PERSON. It is important to inspect and clean the heat exchanger once a year, or as necessary, to remove any build-up of soot. A layer of soot on the inside of the heat exchanger will act as an insulator and reduce heat transfer, resulting in less efficiency.
Reassemble the furnace to its original construction. Remount the burner being certain that the air tube is properly inserted into the chamber opening (see section E). If heavy soot deposits were found in the heat exchanger, this may indicate the burner is out of adjustment. III.
All installations and services must be performed by qualified service personnel. 4. Turn service switch to furnace "ON". If burner starts and runs, but stops again on lockout, it may be necessary to bleed the lines or make burner combustion air adjustments. Contact a qualified service person to adjust and start burner.
Page 14
COMBUSTION AND EFFICIENCY TESTING FOR THERMO PRIDE OIL FIRED CENTRAL FURNACES. Complete this form for each Thermo Pride furnace installed. Read instruction manual carefully before making tests. Retain this form with furnace. CUSTOMER NAME ADDRESS CITY, STATE BURNER MODEL NO. HEATING SYSTEM COMBUSTION CHAMBER...