Before making connections, power down the control panel.
Phone Line
Use a standard RJ31X phone jack (CA38A in Canada) and direct-connect cord as described in the
control's instructions.
1. Connect the direct-connect cord's red and green wires to the control's incoming phone line
terminals as described in the control's instructions.
2. Connect the direct-connect cord's brown and gray wires to TeleSMART's "Home Phones"
terminals, disconnecting them from the control's premises phone terminals, if previously connected.
3. Connect the control's local phone TIP and RING terminals to TeleSMART's "From Control"
terminals, using jumper wires (not supplied).
Speaker: Connect an 8 Ohm speaker to TeleSMART's speaker terminals as shown.
Keypad and Setting the Keypad Address
Connect keypads intended to be used with TeleSMART to the TeleSMART module. Use
addressable, TeleSMART compatible keypads (6162, 6139T). Keypads used only for security
system functions should be connected to the security system's keypad terminals.
1. Disconnect those keypads intended to be used with TeleSMART from the control's terminals,
if previously connected, then connect these keypads to TeleSmart terminals as shown.
NOTE: Run audio cable in separate 2-conductor twisted-pair cable (22AWG recommended).
This cable should be kept at least 6 inches from other types of cables carrying potentially
interfering signals, such as AC power, telephone, and polling loop cables.
2. Set the keypad address, tamper option, and playback volume setting by pressing and holding
the [1] and [3] keys at the same time for 3 seconds, then follow the prompts. You must press
these keys within 60 seconds of power-up to set the address and/or tamper option; you can set
the volume at any time after power-up. Refer to the instructions included with the keypad..
You can set TeleSMART keypads to addresses 2-22, 25-30 (addresses 0, 1, 23, 24 are reserved).
IMPORTANT: If using VISTA-50P or higher, you must program the following two device
addresses when programming the control: address 23 = set as alpha keypad; address 24 = set as
TeleSmart Module.
Control Panel Connections
TeleSMART is powered from the control's +12VDC keypad terminal. Connect the control's
keypad connection terminals to the TeleSMART Control terminals as shown.
Real-Time Clock (RTC) Connection (optional)
This connection is used to drive the TeleSMART internal clock. Connect either terminal of the
control's AC input terminals to the TeleSMART RTC terminal.
Ground Connections: Connect the TeleSMART ground terminal to a good earth ground.