Huawei PDU8000-0125DCV8-BXA001 User Manual page 20

Battery circuit breaker box
Table of Contents

Advertisement

PDU8000-(0125, 0250, 0400, 0630, 0800)
DCV8-BXA001 Battery Circuit Breaker Box
User Manual
Number of
Terminal
Terminals
and Hole
Diameter
UPS+
1 x M10
(through-hole)
UPS N
1 x M10
(through-hole)
1 x M10
UPS–
(through-hole)
BAT+
1 x M10
(through-hole)
BAT N
1 x M10
(through-hole)
BAT–
1 x M10
(through-hole)
PE
1 x M8 (rivet
nut)
PDU8000-0400DCV8-BXA001 Cables
Table 3-3 Specifications for PDU8000-0400DCV8-BXA001 cables and terminals
Number of
Terminal
Terminals and
Hole Diameter
UPS+
1 x M12
(through-hole)
UPS N
1 x M12
(through-hole)
1 x M12
UPS–
(through-hole)
BAT+
1 x M12
(through-hole) or
4 x M10
(through-hole)
BAT N
1 x M12
(through-hole) or
4 x M10
(through-hole)
BAT–
1 x M12
(through-hole) or
Issue 03 (2019-05-20)
Recommended
Recommended
Cable
Wiring
Specifications
Terminal
2
1 x 95 mm
95-M10
2
1 x 95 mm
95-M10
2
1 x 95 mm
95-M10
2
1 x 95 mm
95-M10
2
1 x 95 mm
95-M10
2
1 x 95 mm
95-M10
2
1 x 35 mm
35-M8
Recommended
Recommende
Cable
d Wiring
Specifications
Terminal
2
1 x 150 mm
150-M12
2
1 x 150 mm
150-M12
2
1 x 150 mm
150-M12
2
1 x 150 mm
or 1
150-M12 or
2
x (2 x 70 mm
)
70-M10
2
1 x 150 mm
or 1
150-M12 or
2
x (2 x 70 mm
)
70-M10
2
1 x 150 mm
or 1
150-M12 or
2
x (2 x 70 mm
)
70-M10
Copyright © Huawei Technologies Co., Ltd.
Bolt
Recommended
Specifications
Cable Color
M10 x 40
Red
M10 x 40
Blue
M10 x 40
Black
M10 x 40
Red
M10 x 40
Blue
M10 x 40
Black
M8 x 25
Green-and-yellow
Recommended
Recommended
Bolt
Cable Color
Specifications
M12 x 45
Red
M12 x 45
Blue
M12 x 45
Black
M12 x 45 or 2 x
Red
(M10 x 40)
M12 x 45 or 2 x
Blue
(M10 x 40)
M12 x 45 or 2 x
Black
(M10 x 40)
3 Installation
15

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents