Notice The purchased products, services and features are stipulated by the contract made between Huawei and the customer. All or part of the products, services and features described in this document may not be within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information, and recommendations in this document are provided "AS IS"...
If cables are provided by customers, the cables must be double-insulated and meet 1000 V DC voltage withstanding and current-carrying capacity requirements. PDU8000-0125DCV8-BXA001 Cables Table 3-1 Specifications for PDU8000-0125DCV8-BXA001 cables and terminals Terminal Number of Recommended Recommended...
Page 50
0.90. When the operating temperature of the PDU8000-0125DCV8-BXA001, PDU8000-0250DCV8-BXA001, and PDU8000-0400DCV8-BXA001 is greater than 60° C, the rated current decreases by 5 A for each additional 1° C and is derated to 0.88 at a maximum 70° C.