Installation Instructions
SAFETY INSTRUCTIONS
BREAKERS TYPES
FJ6(ETI), F6, HF6, FM6, FMK, CLF(ETI), HFJ6,
(H)(H)FXD6(ETI), FD6, (H)(H)FD6, CFD6(ETI), FFC, FFF
NOTE: This instruction outlines the recommended
installation procedure.
1. Circuit Breaker Preparation
The circuit breaker should be in the OFF/"O"
position before installing the plug-in-tulip adapter
kit. Turn off and lock out all power supplying
this device before installing. Verify that NO volt-
age is present before proceeding with task.
Hazardous voltage.
Will cause death or
serious injury.
Turn OFF and lock out all
power supplying this
device before installing
or servicing accessory.
Item: Instructions for Installation of Circuit Breaker
Plug-In Adapters. Cat. No.'s TCF2
(2-Pole) and TCF3 (3-Pole).
For use with: SIEMENS
ers and Molded Case Switches in conjunction with
plug-in-tulip connector assemblies. Cat. No.'s
PC4753, PC4754 and PM4754
Page 1 of 3
Pc. No. 410902A01
Remove Pressure Wire Connectors From
Breaker If Present
2. Place tulip clip assembly (6) on back of breaker
in recess provided in base molding. Secure in
place with 5/16 flatwashers (7), lockwashers (8)
and 5/16 - 18 X 1 1/2 round head screws (9)
furnished. (Exception - on CLF and CFD break-
ers use 2" long screws on load side.) Torque
screws to 5-6 lb-Ft. [6.78-8.13 N/m] to assure a
good electrical connection. Repeat this proce-
dure for the remaining tulip clip assemblies.
3. Slide upper end shields (10) and insert lower
end shields (11) with beveled end facing breaker
and press into slots provided at line and load
end of breaker.
4. Add accessory label (12) to top of breaker as
indicated in Fig. 4.
Install As Shown
Fig. 4
®
FD Frame Circuit Break-

Advertisement

loading

Summary of Contents for Siemens TCF2

  • Page 1 Item: Instructions for Installation of Circuit Breaker Plug-In Adapters. Cat. No.’s TCF2 (2-Pole) and TCF3 (3-Pole). For use with: SIEMENS ® FD Frame Circuit Break- ers and Molded Case Switches in conjunction with plug-in-tulip connector assemblies. Cat. No.’s PC4753, PC4754 and PM4754 Page 1 of 3 Siemens Energy &...
  • Page 2 Siemens Energy & Automation, Inc. Bellefontaine, OH 43311 U.S.A. Hazardous voltage. Will cause death or severe injury. Turn OFF and lock out all power supplying this device before installing or servicing accessory. 2 of 3 Page 410902A01 Pc. No. Installation Instructions...
  • Page 3 Turn OFF and lock out all power supplying this device before installing or 3 of 3 Page servicing accessory. 410902A01 Pc. No. © Siemens Energy & Automation, Inc. Installation Instructions TCF2 5.00-6.00 Ft.-lbs. TCF3 6.78-8.13 N/m 6 x 11 4 x 11...

This manual is also suitable for:

Tcf3